1

Nehéz

Why do liquid and oil separators in CO₂ systems require particular attention?


Because CO₂ needs no lubrication, so oil separators are unnecessary
Because of very high pressures – adequate PS and protection devices are required
Because sight glasses and level indicators must not be used in CO₂ systems
Because CO₂ is flammable and separators must not be used

2

Nehéz

What is the critical pressure of CO₂ (R744)?


Approx. 120 bar
Approx. 74 bar (abs)
Approx. 31 bar
Approx. 10 bar

3

Nehéz

What characterises the transcritical process in CO₂ systems?


Heat rejection takes place above the critical point – the refrigerant does not condense in the conventional way (gas cooler instead of condenser)
It occurs only at low temperatures
Conventional condensation occurs
It is irrelevant to system operation

4

Nehéz

What characterises the subcritical CO₂ process?


The absence of condensation
The conventional condensation process below the critical point
The absence of evaporation
Operation above the critical point

5

Könnyű

What is the log(p)-h diagram for CO₂ used for?


To regulate pressure
For analysing thermodynamic processes in a refrigeration system
To measure temperature
To detect leaks

6

Könnyű

What can be read from the log(p)-h graph?


Pressure, enthalpy, temperature and state of the refrigerant
Only the temperature
Only the humidity
Only the amount of refrigerant

7

Könnyű

What are CO₂ saturation tables used for?


To determine the relationship between temperature and pressure at saturation
To regulate the compressor
To measure humidity
To determine the oil quantity

8

Könnyű

What does the CO₂ saturation state mean?


Dry ice state
A state of high pressure
A state in which the refrigerant is only a gas
Equilibrium between the liquid and vapour phases

9

Nehéz

When can dry ice (solid CO₂) form?


At high pressure
During normal operation of the system
When the pressure drops suddenly below the triple point (approx. 5.2 bar abs, −56.6 °C), e.g. when venting liquid CO₂ or charging liquid into an evacuated system
At high temperature

10

Nehéz

What risks are associated with dry ice forming in a CO₂ system?


Pressure reduction
Improved efficiency
No risk
Blocked pipes and valves and system damage (and a sharp pressure rise when it thaws)

11

Nehéz

How does CO₂ saturation pressure change as temperature increases?


It decreases
It first decreases, then increases
It increases rapidly
It remains the same

12

Könnyű

Why is understanding the log(p)-h graph particularly important for CO₂?


It is only used for design purposes
It only applies to NH₃
As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It doesn’t matter

13

Nehéz

What happens to CO₂ above the critical point?


It turns into a liquid
It ceases to conduct heat
It transitions to a supercritical state (no distinction between liquid and gas)
It turns into a solid

14

Könnyű

Why do CO₂ systems require precise pressure control?


Due to low pressures
Because there are no valves
Due to significant pressure changes with temperature fluctuations
They do not require control

15

Nehéz

What is the main characteristic of R744 (CO₂) refrigeration systems?


Very high operating pressures
Low energy efficiency under all conditions
Low operating pressures
No need for control

16

Nehéz

What are the requirements for piping materials in CO₂ systems?


It doesn't matter
They must withstand high pressures (e.g. stainless steel, high-strength copper-alloy tubes such as K65)
Only plastics
Any material may be used

17

Nehéz

How does a booster system work in CO₂ installations?


It is used to store refrigerant
It reduces the refrigerant quantity
Low-temperature (LT) compressors discharge into the suction of medium-temperature (MT) compressors – two-stage compression in a single circuit
It reduces evaporator pressure

18

Könnyű

What is the function of high-pressure control valves in CO₂ systems?


They are used to store the refrigerant
They regulate oil flow
They lower the evaporator temperature
They control the pressure on the high-pressure side and optimise system operation

19

Nehéz

Why is pressure optimisation in CO₂ systems crucial?


It doesn’t matter
It enables the system to achieve maximum energy efficiency in transcritical mode
It reduces the ambient temperature
It reduces the amount of refrigerant

20

Nehéz

What role does parallel compression play in CO₂ systems?


It compresses flash gas from the intermediate receiver directly to high pressure, improving efficiency
It lowers the ambient temperature
It has no significance
It increases energy consumption

21

Nehéz

How does an ejector work in a CO₂ system?


It lowers the evaporator temperature
It increases the amount of refrigerant
Stores the refrigerant
It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency

22

Nehéz

What is the function of liquid ejectors in CO₂ systems?


They reduce atmospheric pressure
They raise the refrigerant temperature
They return liquid from the separator and allow partially flooded evaporator operation (better evaporator feed)
They increase the amount of oil

23

Nehéz

What are the characteristics of partially flooded systems in CO₂ systems?


The presence of liquid in the evaporator, which improves heat transfer and efficiency
The absence of liquid in the evaporator
Lack of regulation
Low operating pressure

24

Nehéz

What is the main risk associated with standstill pressure in CO₂ systems?


A pressure rise as the refrigerant warms up during standstill (possibly exceeding PS and lifting the relief valves)
A drop in temperature
Increased efficiency
A decrease in refrigerant quantity

25

Nehéz

How is standstill pressure limited in CO₂ systems?


By using an auxiliary standstill (stagnation) cooling unit, e.g. cooling the receiver, with back-up power, and by selecting an adequate PS and relief valves
By increasing the refrigerant charge
By completely shutting down the system and power supply
By raising the plant-room temperature

26

Nehéz

What does standstill (stagnation) of a CO₂ system mean, and why is it important?


Improved efficiency
Normal system operation
A state with no compressor operation or refrigerant flow – pressure rises with ambient temperature and may exceed PS
A drop in system temperature

27

Könnyű

Why do CO₂ systems require more advanced automation than traditional systems?


Due to low pressures
They do not require automation
Due to the need for precise control of pressure and temperature
Because there are no valves

28

Nehéz

Which safety class applies to R744?


B2L
A2.
A1
A3

29

Nehéz

In a simple single-stage R744 system without an intermediate receiver (refrigerant flows from the gas cooler directly to the expansion valve), operating transcritically at 90 bar with a gas-cooler outlet temperature of 35 °C, the refrigerant upstream of the expansion valve is…


…a subcooled liquid
…a two-phase mixture at intermediate pressure
…a supercritical fluid
…saturated vapour at intermediate pressure

30

Nehéz

In R744 transcritical systems, the gas cooler outlet valve controls:


The gas cooler fans
The outlet temperature of the gas cooler
The inlet temperature to the gas cooler
The pressure in the gas cooler

31

Nehéz

What is the main reason for using K65 copper tubing in some R744 systems?


They can withstand higher pressures
They bend easily
They come in a wider range of diameters
They have good low-temperature performance

32

Nehéz

Why should an evacuated R744 system initially be charged with refrigerant in the vapour phase?


To prevent dry ice forming (until approx. 5.2 bar abs is exceeded)
To charge R744 more slowly and measure it more accurately
To avoid damaging the compressor with liquid CO₂
To prevent the drain valve on the receiver from opening

33

Nehéz

If moisture remains in an R744 system because it was not properly evacuated (dehydrated), what is the likely consequence?


Formation of hydrogen fluoride and hydrofluoric acid
Reduced cooling capacity
Excessive discharge pressure
Formation of carbonic acid, which damages the system

34

Nehéz

The pressure of R744 at a saturation temperature of 20 °C is approx.


14 bar g
56 bar g
25 bar g
90 bar g

35

Nehéz

At an ambient temperature of 25 °C, the standstill pressure in the low-pressure stage of an R744 cascade (without standstill cooling) will typically be…


…higher than the maximum allowable pressure (PS) of the low-pressure stage
…approx. 27.5 bar g
…the same as the relief valve set pressure
…the same as the high-pressure switch setting

36

Nehéz

What is the correct definition of critical temperature?


The temperature at which, for certain substances, electrical resistance is zero
The temperature at which a substance changes from a gaseous to a solid state
The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature above which there are no distinct liquid and gaseous phases

37

Nehéz

In the gas cooler of a transcritical system, the supercritical working fluid…


…rejects heat at constant temperature and pressure
…rejects heat as its pressure falls
…rejects heat as its temperature falls
…rejects heat during a phase change

38

Közepes

What hazard does a large CO₂ leak in an enclosed room pose to people?


Accumulation near the floor and asphyxiating/toxic effects at high concentrations
CO₂ is completely safe
Explosion of the mixture with air
Formation of hydrogen fluoride

39

Nehéz

Why does the efficiency of transcritical CO₂ systems fall in warm climates, and how is this mitigated?


Efficiency does not depend on climate
Gas cooler pressure drops – extra charge is added
At high ambient temperatures the system operates transcritically with large throttling losses – parallel compression and ejectors are used, among others
CO₂ freezes in the gas cooler – heaters are used