1

Nehéz

What additional protective equipment will you use when brazing systems containing HC refrigerants?


Latex gloves
A flammable gas detector
Ear defenders
A high-visibility vest

2

Nehéz

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


Dust and moisture may enter
There is a risk of refrigerant leakage
It is a potential source of ignition
The pressure switch setting will not be correct

3

Nehéz

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no sources of ignition?


0.5 m
3 m
2 m
1 m

4

Nehéz

What is the maximum safe R32 fill of a recovery cylinder approved for flammable gas that holds 20 kg of R410A (the liquid density of R32 is about 8-10% lower)?


18 kg
9 kg
20 kg
33 kg

5

Nehéz

What is the maximum charge of an A3 refrigerant for a hermetic display cabinet with an integral condenser located in the ground-floor sales area of a supermarket?


1.0 kg
10 kg
2.5 kg
0,494 kg

6

Nehéz

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Place the pump directly on the floor, as low as possible
Ignition-source-free pump, good ventilation, exhaust to a safe place
Position the pump at least 3 m above floor level
Such systems need not be evacuated before charging

7

Nehéz

What safety measure must you carry in your vehicle when transporting flammable refrigerant cylinders?


Tinted safety goggles
A fire blanket
Thick gloves
A fire extinguisher

8

Nehéz

How would you prepare a 10 kg R32 water chiller located outdoors for debrazing its joints?


Vent the R32 outdoors, then fill and vent the system with nitrogen three times
Recover the R32 to a vacuum, then fill the system with nitrogen to a slight positive pressure (approx. 0.1 bar g)
Vent the R32 outdoors and purge the system
Recover the R32 to a vacuum and start desoldering immediately

9

Közepes

What is R1270?


Isobutane
Propene (propylene)
n-Butane
Propane

10

Nehéz

Which of the following leak detection methods should NOT be used to locate an HC refrigerant leak?


Electronic leak detector for flammable refrigerants
Leak detection foam
Soapy water solution
Electronic HFC leak detector

11

Nehéz

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


A different colour for the station
Different connection sizes
Different low-pressure switch setting
A flammable refrigerant recovery unit has no ignition sources

12

Nehéz

Which of the following is a source of ignition?


An Ex-certified fan motor
An 'n'-type (non-sparking) thermostat
A sealed NTC temperature sensor
A contactor (sparking contacts)

13

Nehéz

What particularly hazardous substance is formed when R32 burns?


Phosgene
Hydrogen fluoride (HF)
Hydrogen chloride (HCl)
Sulphur dioxide (SO₂)

14

Nehéz

What type of refrigerant is R1234ze(E)?


HFO (hydrofluoroolefin)
HCFC (hydrochlorofluorocarbon)
CFC (chlorofluorocarbon)
HC (hydrocarbon)

15

Nehéz

What hazards does a safety group A3 refrigerant pose?


Lower toxicity, higher flammability
Higher toxicity, higher flammability
Lower toxicity, moderate flammability
Higher toxicity, moderate flammability

16

Nehéz

According to EN 378, what is the maximum R290 charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL of R290 = 0.038 kg/m³, access category a, location class I, no additional measures))?


0.285 kg
4.93 kg
1.5 kg
1.0 kg

17

Nehéz

What is the approximate ratio of the volumetric cooling capacity of R32 to that of R410A (same compressor and conditions)?


approx. 0.75
approx. 1.05–1.1
approx. 1.3
approx. 0.6

18

Nehéz

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


Because they must be kept running continuously to disperse the leaking refrigerant
Because they are more energy-efficient
Because they are more reliable
To avoid a source of ignition in the event of a flammable refrigerant leak

19

Nehéz

Why is the density difference between HC and HFC refrigerants important?


Because it determines the system's energy efficiency
Because HCs must be charged much more slowly than HFCs
An HC charge in kg is roughly half that of an HFC
Because HCs operate at much higher pressures

20

Nehéz

What is the GWP of R290 according to Annex VI to Regulation (EU) 2024/573?


675
7
150
0.02

21

Nehéz

Which of the following is NOT a source of ignition?


An electrical switch
An Ex-certified fan motor
An unsealed mechanical pressure switch
A light switch

22

Nehéz

What is R290?


Butane
Propene (Propylene)
Propane
Isobutane

23

Nehéz

What is the maximum A2L charge for a hermetic display cabinet with integral condenser in the ground-floor sales area of a supermarket?


1.2 kg
1.5 kg
2.5 kg
150 g

24

Nehéz

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


Current consumption differs for compressors using flammable refrigerants compared to those using HFCs
A relay is never required for compressors using flammable refrigerants
The method of starting the compressor motor differs from that used with HFCs
It could be a source of ignition

25

Nehéz

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no ignition sources?


3 m
1 m
10 m
5 m

26

Nehéz

A recovery cylinder holds 10 kg of R404A (filling ratio 0.82 kg/l). What is the maximum R290 charge for this cylinder (propane filling ratio 0.43 kg/l per ADR P200)?


approx. 8 kg
approx. 5.2 kg
approx. 17 kg
20 kg

27

Nehéz

How can a vacuum pump be used safely to evacuate a system containing R290?


Place the pump directly on the floor, as low as possible
Position the pump at least 3 m above floor level
R290 systems need not be evacuated before charging
Ignition-source-free pump, good ventilation, exhaust to a safe place

28

Nehéz

Under ADR, what equipment must you carry in your vehicle when transporting flammable refrigerant cylinders (under the 1.1.3.6 exemption)?


Tinted safety goggles
A fire extinguisher (at least 2 kg dry powder)
A fire blanket
Thick gloves

29

Nehéz

How do you make sure it is safe to light the torch for desoldering joints in a system from which a flammable refrigerant has been removed?


Purge the system with compressed air
Such joints must never be desoldered; they must be cut with a pipe cutter
Ensure good ventilation and check the work area with a flammable gas detector
Working outdoors is sufficient

30

Nehéz

How would you prepare a system containing 100 g of R1270 for debrazing, if local regulations allow controlled venting of small HC quantities?


Vent the R1270 to a safe outdoor location, then purge with OFN three times (pressurise and vent), and braze with OFN flowing
Vent the R1270 into the room and open a window
Vent the R1270 outdoors and start brazing immediately
Recover the R1270 to a vacuum and start brazing immediately without a nitrogen purge

31

Nehéz

Which method should NOT be used to locate an R290 leak?


An electronic leak detector designed for HFCs
Leak detection foam
An electronic detector for flammable refrigerants
Fluorescent dye and UV lamp (if approved by the manufacturer)

32

Nehéz

Why can’t recovery stations designed for HFCs be used with R600a?


The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure
They contain ignition sources
The oil in the recovery unit is not soluble in R600a
The recovery unit cannot withstand the working pressure of R600a

33

Nehéz

According to EN 378, what is the maximum R1234ze(E) charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL = 0.303 kg/m³, access category a, location class I, no additional measures)?


2.27 kg
618 kg
227 kg
6.18 kg

34

Nehéz

What type of refrigerant is R32?


Hydrofluorocarbon
Hydrofluoroolefin
Hydrocarbon
Carbon dioxide

35

Nehéz

What hazards do A2L refrigerants pose?


Lower toxicity, higher flammability
Higher toxicity, lower flammability
Higher toxicity, higher flammability
Lower toxicity, lower flammability (burning velocity ≤ 10 cm/s)

36

Nehéz

What hazard is associated with the combustion of HFO or HFC refrigerants?


Hydrogen fluoride (HF) is formed
Phosgene is formed
Ozone is formed
Nitrous oxide is formed

37

Nehéz

Approximately what compressor displacement is required for R600a compared with R134a for the same cooling capacity?


About twice as large
About half
About seven times as large
The same

38

Nehéz

What is the GWP value for R32 according to Regulation (EU) 2024/573?


0
675
7
3

39

Nehéz

Why is charge accuracy more important in critically charged R290 systems than in HFC systems?


Because such systems never have liquid receivers
Because of lower operating pressures
Because R290 is only used in systems below 150 g
The charge mass is much smaller than in an HFC system, because the liquid density of R290 is much lower

40

Nehéz

Why does the condenser fan run continuously in some systems using R1270?


To ensure that the discharge pressure never becomes excessive
To reduce energy consumption
To dilute the refrigerant in the event of a leak
To prevent the build-up of contaminants in the condenser

41

Közepes

What is the main design difference in hydrocarbon refrigeration systems?


Higher operating pressures
Lower energy efficiency
No need for safety measures
The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability

42

Közepes

How do compressors used in hydrocarbon systems differ?


There is no difference
They must operate at higher pressures than HFC compressors
They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)
They need no lubrication

43

Nehéz

What must the label of a flammable refrigerant cylinder include?


Information about the cylinder owner
The refrigerant name, the UN number, the hazard label (e.g. 2.1 – flammable gas) and basic safety information
Only the net weight
Only the refrigerant name

44

Nehéz

Why is the absence of a 'flammable refrigerant' label on equipment a serious hazard?


It may lead to the wrong oil being selected
It has no significant effect on safety
It may lead to the use of tools that are ignition sources
It reduces system efficiency

45

Nehéz

Which set of information on the label of a flammable refrigerant cylinder is crucial from a safety perspective?


Manufacturer’s name and country of origin
Gross weight and batch number
Name of the substance, hazard label (ADR) / GHS pictogram (CLP), UN number
Cylinder colour and date of manufacture

46

Könnyű

What is the requirement regarding the labelling of an installation containing a flammable substance?


Colour-coding of pipes is sufficient
The labelling must indicate the type of substance and the flammability hazard
Labelling is not required for hermetically sealed systems
Labelling is required only in technical rooms

47

Könnyű

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


Risk of leakage and the formation of an explosive mixture
No impact on safety
Merely a reduction in efficiency
Merely installation difficulties

48

Nehéz

What is the purpose of gas detectors in a room with a refrigeration system?


Monitoring pipe pressure
Early leak detection and triggering of measures preventing health risks and explosive atmospheres (alarm, ventilation, shut-off)
Controlling compressor capacity
Measuring refrigerant temperature

49

Nehéz

How often should gas detection sensors in a machinery room be checked?


Before every start-up of the unit
According to the manufacturer's instructions and regulations – at least every 12 months
Only after a leak has occurred
Once every 5 years

50

Nehéz

Where should a gas detector be located according to EN 378?


Where the refrigerant would accumulate: low (near the floor) for refrigerants heavier than air, high (near the ceiling) for lighter ones such as NH₃
Anywhere in the room
Near the control panel
Only at the room entrance

51

Könnyű

How should an employee respond when a gas alarm is triggered?


Switch off the system and wait for the alarm to stop
Reduce the pressure in the system
Carry on working until they see a leak
Leave the room immediately and notify their supervisor

52

Nehéz

What safety checks should be carried out when installing a new refrigeration system with a flammable refrigerant?


The colour of pipes and hoses
Only that the air filter is new
Only the compressor power
The presence of health and safety signage, adequate ventilation and gas detectors

53

Könnyű

Gas detectors should be installed in rooms where:


Ventilation is natural
The room is less than 5 m²
The amount of refrigerant exceeds a specified permissible threshold
Any refrigerant is present, regardless of the quantity

54

Nehéz

What are the requirements for emergency exits from a refrigeration machinery room?


One exit with a sign stating the refrigerant type is sufficient
In small machinery rooms emergency exits need not be signed
Outward-opening doors and signed escape routes (number of exits per the standard)
At least two exits are required and signage is optional

55

Nehéz

Which installation measure for a flammable-refrigerant system improves its energy efficiency?


Omitting the filter-drier
Charging above the nameplate quantity
Restricting room ventilation
A thorough tightness test and evacuation (dehydration) of the system

56

Könnyű

How do leaks affect systems using flammable refrigerants?


They improve efficiency
They lower the temperature
Have no effect
They cause refrigerant loss, reduced efficiency and a fire hazard

57

Nehéz

Why is it important to limit the refrigerant charge in HC systems?


It limits the possibility of reaching a flammable concentration (≥ LFL) in a leak, increasing safety
It increases capacity
It lowers the temperature
It doesn't matter

58

Könnyű

Why is the cleanliness of heat exchangers in HC systems important?


Causes leaks
It improves heat transfer and reduces energy consumption
It increases the pressure
It doesn’t matter

59

Könnyű

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Increasing the refrigerant charge
Regular checks for leaks and operating parameters
Lack of servicing
Disabling safety devices

60

Könnyű

How does the correct selection of components affect a system using a flammable refrigerant?


It increases the amount of refrigerant
It ensures safe and optimal operation and minimises energy losses
It doesn’t matter
It lowers the temperature

61

Könnyű

Why is it important to use the correct service tools in HC systems?


It doesn’t matter
It ensures operational safety and reduces refrigerant losses
It increases energy consumption
Causes leaks

62

Könnyű

How does pipe insulation affect the efficiency of systems containing HC?


It reduces energy losses and improves efficiency
Causes leaks
It increases the pressure
It doesn’t matter

63

Nehéz

What hazards are associated with a safety group A3 refrigerant?


Lower toxicity, no flame propagation
Lower flammability, lower toxicity
Higher toxicity, no flame propagation
Higher flammability, lower toxicity

64

Nehéz

What is the GWP of R32 (per AR4, as used in Regulation (EU) 2024/573)?


3922
675
0
6

65

Nehéz

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Lower flammability limit, room volume
Lower flammability limit, height of the indoor unit, floor area
Practical limit, room volume
Practical limit, height of the indoor unit, floor area

66

Nehéz

What compressor displacement is required for R1270 compared with an R404A compressor in the medium-temperature range (cold room)?


About 6 times larger
About 1.5 times larger
Similar
About half

67

Közepes

What distinguishes class 2L refrigerants from class 2?


Heat of combustion above 19 MJ/kg
No lower flammability limit
A maximum burning velocity of no more than 10 cm/s
Higher toxicity

68

Közepes

What is the lower flammability limit (LFL) of propane R290?


Approx. 1.8 kg/m³
Approx. 0.038 kg/m³ (approx. 2.1% by volume)
Approx. 0.307 kg/m³
Approx. 0.38 kg/m³

69

Nehéz

What is the maximum R290 charge per circuit of a commercial refrigerating appliance (e.g. a cabinet) according to EN IEC 60335-2-89:2022?


1.2 kg
13 × LFL ≈ 494 g
1.5 kg
150 g

70

Nehéz

Calculate the maximum R32 charge (LFL = 0.307 kg/m³) for a wall-mounted air conditioner (h₀ = 1.8 m) in a 20 m² room using m_max = 2.5 × LFL^1.25 × h₀ × A^0.5.


approx. 13.8 kg
approx. 0.46 kg
approx. 4.6 kg
approx. 1.5 kg

71

Közepes

Equipment marked 'Ex II 3G' may be used in zone:


20 (dusts)
1
0
2 (explosive gas atmosphere unlikely and short-lived)

72

Közepes

How is explosion hazard zone 2 defined?


An explosive atmosphere is likely to occur in normal operation
An explosive atmosphere is present continuously or for long periods
An area where flammable refrigerants are never used
An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period

73

Közepes

Under which UN number is propane (R290) carried under ADR?


UN 1005
UN 1978
UN 3252
UN 3337

74

Nehéz

What is the maximum quantity of R290 (class 2, group F) that may be carried per transport unit under the ADR 1.1.3.6 exemption?


1000 kg
20 kg
333 kg
Unlimited

75

Közepes

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


At 5% propane by volume
At 100% of LFL
At 150% of LFL
No higher than 25% of LFL

76

Közepes

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


Evacuate it (no air) and label it for the specific flammable refrigerant
Partly fill it with nitrogen to 5 bar
No preparation is needed
Purge it with compressed air

77

Közepes

What is the correct approach in a risk analysis before work on an HC system?


First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)
First select PPE, then possibly remove ignition sources
The risk analysis is done after the work is finished
Having a fire extinguisher is sufficient

78

Nehéz

What is the charge limit m₃ = 130 m³ × LFL for R290 (LFL = 0.038 kg/m³) according to IEC 60335-2-40?


approx. 0.99 kg
approx. 13 kg
approx. 0.15 kg
approx. 4.94 kg

79

Közepes

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Because scales are not needed – charging is done by sight glass
Because extra R290 improves efficiency
Because R290 is more expensive than HFCs
Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak