1

Könnyű


2

Könnyű

What is the base unit of mass in the International System of Units (SI)?


N
kg
t
lb (pound)

3

Közepes

What process takes place in the condenser of a refrigeration system?


The refrigerant absorbs heat from the surroundings and evaporates
The secondary fluid (glycol, water) condenses while the refrigerant evaporates
Hot vapour discharged by the compressor is desuperheated, condensed, and the resulting liquid is slightly subcooled
The refrigerant rejects only the heat generated in the compressor

4

Közepes

What mainly determines the condensing temperature of an air-cooled condenser?


The superheat
The compressor discharge temperature
The ambient (inlet) air temperature
The evaporating temperature

5

Közepes

Why does heat flow from the condenser to the surroundings?


Because the condensing temperature is higher than the ambient temperature, and heat flows spontaneously from a warmer to a colder body (second law of thermodynamics)
Because HFC refrigerants attract heat from the surroundings
Because the pressure in the condenser is lower than ambient
Because the compressor pushes heat directly into the surroundings

6

Közepes

What should you mainly pay attention to when operating a condenser?


That the outlet air temperature is higher than the condensing temperature
That the inlet air temperature is lower than the outlet air temperature
Its general condition and the cleanliness of the heat-exchange surfaces
The colour of the condenser casing

7

Közepes

What criteria should be considered when selecting a suitable condenser?


Only own experience and the dimensions
The required capacity of the condenser and the technical specifications declared by the manufacturer
Fan noise, connection diameters and colour
Only the size and number of fans

8

Közepes

How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?


Contaminants increase the heat transfer area and reduce the condensing pressure.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure.
Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers.

9

Közepes

How does the capacity of an air-cooled condenser change when it becomes dirty?


It increases because the fan speed rises
It decreases
It increases
It remains unchanged

10

Közepes

What is the main consequence of heavy frost on an air-cooling evaporator?


An increase in condenser subcooling
Reduced heat transfer and airflow, resulting in a drop in cooling capacity and evaporating temperature
A rise in evaporating pressure
A rise in the cooled-air temperature with no effect on capacity

11

Közepes

What happens when the evaporation temperature drops?


The condenser fan speed increases.
The compressor’s cooling capacity increases.
The discharge temperature decreases.
The compressor’s cooling capacity decreases.

12

Közepes

When is natural (off-cycle, air) defrosting possible?


Only in coolers fitted with speed-controlled fans
Only in freezer rooms below −18 °C
Never – electric heaters must be used in every air cooler
When the air passing through the cooler is above 0 °C

13

Közepes

When does frost form on the surface of an air-cooling evaporator?


Always, in every air cooler
Only when the room air temperature falls below 0 °C
When the evaporator surface temperature is below 0 °C and below the dew point of the air
Only when the system runs continuously

14

Közepes

In extensive pipework systems, flash gas (secondary evaporation) in the liquid line can be prevented by…


…using smaller-diameter pipes
…increasing the length of the liquid line
…additional subcooling of the liquid
…insulating the discharge line between the compressor and the condenser

15

Közepes

How does hot gas defrosting of the evaporator work?


This involves reversing the direction of rotation of the compressor.
Heated vapour (hot gas) from the compressor is directed into the evaporator piping.
We swap the outlet and inlet sides of the evaporator.
We switch on the gas heater directed at the evaporator.

16

Közepes

What is the function of the evaporator in a refrigeration system?


It cools the refrigerant.
It ensures that the refrigerant is superheated over the largest possible heat exchange surface area.
It transfers heat from the medium being cooled to the boiling refrigerant.
It evaporates the water flowing through the evaporator.

17

Közepes

What condition must electric heaters for evaporator defrosting meet?


They must be located beneath the evaporator
They must have good thermal contact with the heat-exchange surface (e.g. inserted in the fin block)
They must be in direct contact with the refrigerant
Heat from the heaters must be carried by the running fans

18

Közepes

Refrigerant distributor:


ensures even distribution of the refrigerant to the individual sections of the condenser.
ensures an even distribution of the refrigerant to the individual sections of the evaporator.
ensures the even distribution of the refrigerant discharged by compressors connected in parallel.
acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded.

19

Közepes

What defrosting methods are used for air coolers?


Only by switching off the fans with the compressor running
Electric, hot gas, water spray and natural (at positive temperatures)
Electric only – other methods are not permitted in refrigeration
Natural only – other methods are ineffective and uneconomic

20

Közepes

The boiling point of a liquid rises when the pressure above the liquid…


…rises
…varies depending on the ambient temperature
…falls
…remains constant

21

Közepes

MOP in thermostatic expansion valves stands for:


maximum pressure switch protection.
minimum flow opening.
maximum operating pressure.
self-cleaning of the valve in the event of moisture in the refrigerant freezing.

22

Közepes

The function of a thermostatic expansion valve (TEV) is:


to maintain a constant condensing pressure
to meter refrigerant into the evaporator according to the superheat of the vapour leaving the evaporator
to adjust the evaporating pressure in the condenser
to maintain a constant compressor suction pressure

23

Közepes

What type of compressor motor can be used with a capillary tube?


A low-speed motor
An electronically commutated motor
A low-starting-torque motor (pressures equalise during standstill)
A high-starting-torque motor must be used

24

Közepes

What does a thermostatic expansion valve control?


The temperature in the cold room
The condensing pressure
The discharge temperature
The mass flow of refrigerant fed into the evaporator

25

Könnyű

The refrigerant absorbs heat when…


…it evaporates
…it condenses
…it freezes
…it is subcooled

26

Közepes

What does the manufacturer state as the factory setting of a thermostatic expansion valve?


the degree to which the valve is filled with refrigerant liquid.
the superheat value during valve operation.
the degree of refrigerant expansion.
the static superheat of the valve.

27

Közepes

Where is a new or repaired system with an expansion valve and liquid receiver charged?


In the liquid phase on the high-pressure side, with the compressor stopped
Through the capillary tube outlet during normal system operation
In the liquid phase into the compressor suction, with the compressor running
Anywhere – the charging point does not matter

28

Közepes

What does a thermostatic or electronic expansion valve control?


The compressor speed
Subcooling, by adjusting condensing pressure
The evaporating pressure – closing below the set point
The amount of refrigerant fed to the evaporator according to superheat

29

Közepes

What does the MOP function of thermostatic expansion valves mean?


The valve prevents motor overheating by injecting liquid into the compressor
The valve limits subcooling
The valve limits the maximum evaporating (suction) pressure, protecting the compressor motor from overload, e.g. after defrost
The valve maintains a constant condensing pressure

30

Közepes

The lower the liquid temperature upstream of the expansion valve, (at the same mass flow)…


…the lower qo, with Qo unchanged
…the lower qo and the lower Qo
…the higher the specific refrigerating effect qo [kJ/kg] and the higher the cooling capacity Qo
…the lower qo and the lower energy efficiency

31

Közepes

How should the MOP point of an expansion valve be selected relative to the highest normal evaporating temperature?


A few kelvin higher (approximately 7 K)
Higher by approx. 20 K
About 7 K lower than that temperature
Freely – the MOP value is irrelevant

32

Közepes

What is the function of the suction pressure regulator?


It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system.
To maintain the suction pressure at the highest possible level.
It maintains the evaporation pressure at a constant level.
It limits the suction pressure and protects the compressor from excessively high suction pressure.

33

Közepes

What is the function of the valve regulating water flow through the condenser?


To maintain the condensing pressure at a constant level.
To maintain the condensing pressure at the lowest possible level.
To maintain the water temperature at the highest level.
To maintain the condensing pressure at the highest possible level.

34

Közepes

The use of a refrigerant distributor requires a thermostatic expansion valve ...


... with a MOP function.
... with external pressure equalisation.
... with internal pressure equalisation.
... with an adsorption-type sensor filling.

35

Közepes

What properties should good insulation materials have?


Low thermal conductivity (and low water absorption, vapour tightness)
An antistatic coating
The ability to absorb large amounts of moisture
High thermal conductivity

36

Közepes

When is refrigerant vapour superheated?


When its temperature is higher than the saturation temperature corresponding to its pressure
When the evaporating temperature is lower than the ambient temperature
When the compressor motor temperature rises excessively
When the pressure on the discharge side is higher than on the suction side

37

Közepes

How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?


We check this using a sight glass.
We check using a liquid pressure gauge.
We are unable to check this.
We check using a pressure gauge fitted on the discharge side of the compressor.

38

Közepes

Where does the liquid line run?


Between the evaporator and the suction-line heat exchanger
Between the compressor and the condenser
Between the evaporator and the compressor
From the condenser (liquid receiver) to the expansion valve

39

Közepes

What is the function of the liquid receiver in a refrigeration system?


To act as a reserve when the required charge is unknown
To collect liquid refrigerant and excess oil
To further subcool the condensed refrigerant
To store refrigerant and compensate for changes in the circulating charge as the heat load varies

40

Közepes

What is the purpose of the liquid receiver during service work?


It allows pump-down and temporary storage of the refrigerant
It further subcools the refrigerant before the expansion valve
It collects excess oil circulating in the system
It is a reserve when the installer does not know the required charge

41

Közepes

Where should the liquid receiver be installed?


It should be fitted between the compressor and the condenser.
It should be fitted after the evaporator.
It should be installed downstream of the condenser, upstream of the expansion valve.
It should be fitted just before the compressor.

42

Közepes

What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?


It regulates the condensing pressure.
It opens when the suction pressure upstream of the compressor drops.
It closes when the suction pressure upstream of the compressor drops.
It regulates the evaporation pressure.

43

Közepes

The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:


A reduction in the system’s energy efficiency.
An increase in the amount of refrigerant in the system and an increase in condensing pressure.
There is no effect whatsoever on either the amount of refrigerant or energy efficiency.
A reduction in refrigerant charge and, typically, higher energy efficiency.

44

Közepes

Which refrigerants belong to the HFC group?


R134a, R404A, R507A, R410A.
R22, R401A.
R134a, R32, R22, R507A, R290.
R11, R12, R502.

45

Közepes

Which refrigerants belong to the HFO group?


R134a, R290.
R22, R12.
R134a, R404A.
R1234yf, R1234ze(E).

46

Közepes

What are the characteristics of R410A refrigerant compared to R407C refrigerant?


The saturation pressure of R410A refrigerant is higher than that of R407C.
The saturation pressure of both refrigerants is roughly the same.
The saturation pressure of R407C refrigerant is much higher than that of R410A.
The saturation pressure of R407C is 150% higher than that of R410A.

47

Közepes

What does the TEWI indicator define?


The ability of the ozone layer to recover
The impact of a refrigerant on the ozone layer
The global warming potential of a gas relative to CO₂ over a 100-year horizon
Total Equivalent Warming Impact: the sum of direct emissions (leakage and refrigerant losses at disposal) and indirect emissions (CO₂ from generating the energy consumed by the equipment) over its lifetime

48

Közepes

What are the characteristics of R452A compared with R404A?


It is a non-flammable (A1) HFC/HFO blend with properties similar to R404A and a GWP about 45% lower
It is a flammable and toxic single-component HFC
Both are azeotropic and have no temperature glide
The temperature glide of R452A is half that of R404A

49

Közepes

What distinguishes R1234yf from R134a?


Higher toxicity
It is mildly flammable (class A2L), whereas R134a is non-flammable (A1)
A higher critical temperature
A higher normal boiling point

50

Közepes

How does CO₂ (R744) compare with R134a?


It has identical properties and is a drop-in replacement for R134a
It has a lower critical temperature, much higher operating pressures and a much higher volumetric cooling capacity (smaller compressors and pipes)
Its temperature glide is 7 K greater than that of R134a
Unlike R134a, it is an azeotropic mixture

51

Közepes

Which of the following is NOT a fluorinated greenhouse gas?


Perfluorocarbons (PFCs).
Sulphur hexafluoride (SF6).
Hydrofluorocarbons (HFCs).
Carbon dioxide (CO₂).

52

Nehéz

What additional protective equipment will you use when brazing systems containing HC refrigerants?


Ear defenders
Latex gloves
A flammable gas detector
A high-visibility vest

53

Nehéz

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


There is a risk of refrigerant leakage
The pressure switch setting will not be correct
It is a potential source of ignition
Dust and moisture may enter

54

Nehéz

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no sources of ignition?


0.5 m
2 m
3 m
1 m

55

Nehéz

What is the maximum safe R32 fill of a recovery cylinder approved for flammable gas that holds 20 kg of R410A (the liquid density of R32 is about 8-10% lower)?


9 kg
20 kg
18 kg
33 kg

56

Nehéz

What is the maximum charge of an A3 refrigerant for a hermetic display cabinet with an integral condenser located in the ground-floor sales area of a supermarket?


10 kg
2.5 kg
1.0 kg
0,494 kg

57

Nehéz

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Ignition-source-free pump, good ventilation, exhaust to a safe place
Such systems need not be evacuated before charging
Position the pump at least 3 m above floor level
Place the pump directly on the floor, as low as possible

58

Közepes

What is the greenhouse effect?


Greenhouse gases absorb and re-emit the Earth's infrared radiation, warming the lower atmosphere
Clouds reflect ultraviolet radiation, which makes the air near the surface warmer
Dust in the atmosphere reflects sunlight, lowering the average surface temperature
Chlorine compounds destroy stratospheric ozone, increasing UV radiation at the surface

59

Nehéz

What safety measure must you carry in your vehicle when transporting flammable refrigerant cylinders?


A fire blanket
Tinted safety goggles
A fire extinguisher
Thick gloves

60

Nehéz

How would you prepare a 10 kg R32 water chiller located outdoors for debrazing its joints?


Vent the R32 outdoors and purge the system
Vent the R32 outdoors, then fill and vent the system with nitrogen three times
Recover the R32 to a vacuum and start desoldering immediately
Recover the R32 to a vacuum, then fill the system with nitrogen to a slight positive pressure (approx. 0.1 bar g)

61

Közepes

What is R1270?


n-Butane
Propane
Isobutane
Propene (propylene)

62

Nehéz

Which of the following leak detection methods should NOT be used to locate an HC refrigerant leak?


Electronic leak detector for flammable refrigerants
Leak detection foam
Soapy water solution
Electronic HFC leak detector

63

Nehéz

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


Different low-pressure switch setting
Different connection sizes
A flammable refrigerant recovery unit has no ignition sources
A different colour for the station

64

Nehéz

Which of the following is a source of ignition?


A sealed NTC temperature sensor
A contactor (sparking contacts)
An Ex-certified fan motor
An 'n'-type (non-sparking) thermostat

65

Nehéz

What particularly hazardous substance is formed when R32 burns?


Sulphur dioxide (SO₂)
Hydrogen chloride (HCl)
Phosgene
Hydrogen fluoride (HF)

66

Nehéz

What type of refrigerant is R1234ze(E)?


HCFC (hydrochlorofluorocarbon)
HC (hydrocarbon)
CFC (chlorofluorocarbon)
HFO (hydrofluoroolefin)

67

Nehéz

What hazards does a safety group A3 refrigerant pose?


Higher toxicity, higher flammability
Lower toxicity, higher flammability
Higher toxicity, moderate flammability
Lower toxicity, moderate flammability

68

Nehéz

According to EN 378, what is the maximum R290 charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL of R290 = 0.038 kg/m³, access category a, location class I, no additional measures))?


1.0 kg
1.5 kg
0.285 kg
4.93 kg

69

Könnyű

What does the GWP indicator mean?


Ozone depletion potential
The annual rise in mean air temperature caused by the emission of 1 kg of the gas
Global Warming Potential: the climate warming impact of 1 kg of a gas compared with 1 kg of CO₂ (GWP = 1) over a defined time horizon, usually 100 years
The ability of a substance to restore the ozone layer

70

Nehéz

What is the approximate ratio of the volumetric cooling capacity of R32 to that of R410A (same compressor and conditions)?


approx. 0.6
approx. 0.75
approx. 1.3
approx. 1.05–1.1

71

Nehéz

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


Because they are more energy-efficient
Because they are more reliable
To avoid a source of ignition in the event of a flammable refrigerant leak
Because they must be kept running continuously to disperse the leaking refrigerant

72

Nehéz

Why is the density difference between HC and HFC refrigerants important?


Because HCs operate at much higher pressures
An HC charge in kg is roughly half that of an HFC
Because HCs must be charged much more slowly than HFCs
Because it determines the system's energy efficiency

73

Nehéz

What is the GWP of R290 according to Annex VI to Regulation (EU) 2024/573?


150
675
7
0.02

74

Nehéz

Which of the following is NOT a source of ignition?


An unsealed mechanical pressure switch
A light switch
An Ex-certified fan motor
An electrical switch

75

Nehéz

What is R290?


Butane
Isobutane
Propene (Propylene)
Propane

76

Nehéz

What is the maximum A2L charge for a hermetic display cabinet with integral condenser in the ground-floor sales area of a supermarket?


150 g
1.2 kg
1.5 kg
2.5 kg

77

Nehéz

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


The method of starting the compressor motor differs from that used with HFCs
A relay is never required for compressors using flammable refrigerants
It could be a source of ignition
Current consumption differs for compressors using flammable refrigerants compared to those using HFCs

78

Nehéz

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no ignition sources?


3 m
5 m
10 m
1 m

79

Nehéz

A recovery cylinder holds 10 kg of R404A (filling ratio 0.82 kg/l). What is the maximum R290 charge for this cylinder (propane filling ratio 0.43 kg/l per ADR P200)?


approx. 17 kg
approx. 5.2 kg
20 kg
approx. 8 kg

80

Közepes

How do refrigeration systems contribute to the greenhouse effect?


Through oil emitted into the atmosphere from the condenser and filter
Indirectly (through energy consumption) and directly (through emissions of refrigerant into the atmosphere)
Only through the heat rejected by the condenser
Only through CO₂ given off by the compressor motor

81

Nehéz

How can a vacuum pump be used safely to evacuate a system containing R290?


Place the pump directly on the floor, as low as possible
Ignition-source-free pump, good ventilation, exhaust to a safe place
Position the pump at least 3 m above floor level
R290 systems need not be evacuated before charging

82

Nehéz

Under ADR, what equipment must you carry in your vehicle when transporting flammable refrigerant cylinders (under the 1.1.3.6 exemption)?


A fire extinguisher (at least 2 kg dry powder)
A fire blanket
Tinted safety goggles
Thick gloves

83

Nehéz

How do you make sure it is safe to light the torch for desoldering joints in a system from which a flammable refrigerant has been removed?


Purge the system with compressed air
Such joints must never be desoldered; they must be cut with a pipe cutter
Working outdoors is sufficient
Ensure good ventilation and check the work area with a flammable gas detector

84

Nehéz

How would you prepare a system containing 100 g of R1270 for debrazing, if local regulations allow controlled venting of small HC quantities?


Vent the R1270 to a safe outdoor location, then purge with OFN three times (pressurise and vent), and braze with OFN flowing
Vent the R1270 outdoors and start brazing immediately
Recover the R1270 to a vacuum and start brazing immediately without a nitrogen purge
Vent the R1270 into the room and open a window

85

Nehéz

Which method should NOT be used to locate an R290 leak?


Leak detection foam
An electronic detector for flammable refrigerants
Fluorescent dye and UV lamp (if approved by the manufacturer)
An electronic leak detector designed for HFCs

86

Nehéz

Why can’t recovery stations designed for HFCs be used with R600a?


The recovery unit cannot withstand the working pressure of R600a
The oil in the recovery unit is not soluble in R600a
They contain ignition sources
The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure

87

Nehéz

According to EN 378, what is the maximum R1234ze(E) charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL = 0.303 kg/m³, access category a, location class I, no additional measures)?


227 kg
618 kg
2.27 kg
6.18 kg

88

Nehéz

What type of refrigerant is R32?


Carbon dioxide
Hydrofluorocarbon
Hydrocarbon
Hydrofluoroolefin

89

Nehéz

What hazards do A2L refrigerants pose?


Lower toxicity, lower flammability (burning velocity ≤ 10 cm/s)
Higher toxicity, lower flammability
Lower toxicity, higher flammability
Higher toxicity, higher flammability

90

Nehéz

What hazard is associated with the combustion of HFO or HFC refrigerants?


Ozone is formed
Phosgene is formed
Nitrous oxide is formed
Hydrogen fluoride (HF) is formed

91

Közepes

What is the greenhouse effect?


The absorption of solar radiation by the Earth's surface
The filtering of solar radiation by the atmosphere
The trapping of heat in the Earth's atmosphere, which hinders the radiation of heat into space
The formation of a layer that traps only heat from fuel combustion in aircraft

92

Nehéz

Approximately what compressor displacement is required for R600a compared with R134a for the same cooling capacity?


The same
About twice as large
About half
About seven times as large

93

Nehéz

What is the GWP value for R32 according to Regulation (EU) 2024/573?


7
3
0
675

94

Nehéz

Why is charge accuracy more important in critically charged R290 systems than in HFC systems?


Because R290 is only used in systems below 150 g
Because of lower operating pressures
Because such systems never have liquid receivers
The charge mass is much smaller than in an HFC system, because the liquid density of R290 is much lower

95

Nehéz

Why does the condenser fan run continuously in some systems using R1270?


To ensure that the discharge pressure never becomes excessive
To dilute the refrigerant in the event of a leak
To reduce energy consumption
To prevent the build-up of contaminants in the condenser

96

Közepes

Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?


Regulation (EU) 2024/573
Regulation (EU) No 517/2014
Directive 2009/125/EC
Regulation (EU) 2015/1188

97

Közepes

What is the main objective of Regulation (EU) 2024/573?


To reduce taxes on refrigeration equipment
Standardising metal recycling standards
To facilitate the import of electrical appliances
Prevention of F-gas emissions and the achievement of the EU’s climate targets

98

Közepes

What are the ecodesign obligations of manufacturers of refrigerating appliances?


Meeting implementing regulations (e.g. 2019/2019, 2015/1095): efficiency, spare parts, reparability
Only declaring F-gas quantities under Regulation (EU) No 517/2014
Only implementing an ISO 9001 quality management system
Only using energy labels under Regulation (EU) 2024/573

99

Közepes

What is the main objective of EU ecodesign legislation (Directive 2009/125/EC, now Regulation (EU) 2024/1781 – ESPR)?


To facilitate imports from outside the EU
To reduce the negative environmental impact of products by improving energy efficiency, durability and recyclability
To increase sales of electrical appliances in the EU
To standardise the appearance of products in the EU

100

Közepes

What is the function of a ball valve in a refrigeration system?


It prevents excessive pressure build-up in the system
Enables the refrigerant flow to be completely shut off
It measures the moisture content of the refrigerant
It regulates the temperature of the refrigerant

101

Könnyű

What is the main function of a safety valve?


It controls the oil level in the compressor
Prevents the evaporator from freezing
It monitors the moisture content of the refrigerant
Discharges refrigerant when the set pressure is exceeded

102

Közepes

How do certain gases contribute to the greenhouse effect?


They deplete the ozone layer, so more solar radiation reaches the surface
They heat the air through chemical reactions with atmospheric oxygen and nitrogen
They limit UV radiation reaching the Earth's surface, changing the heat balance
They trap thermal radiation that the Earth would otherwise emit into space

103

Közepes

What is the purpose of a sight glass (with moisture indicator)?


Regulating compressor pressure
Measuring condenser temperature
Visual assessment of the refrigerant condition in the liquid line (bubbles) and of system moisture
Emergency shut-off of flow

104

Közepes

What is the function of the temperature regulator in a refrigeration system?


Controls the operation of the compressor and valves to maintain the set temperature
It restricts oil flow
To maintain a constant pressure in the compressor
It drains excess refrigerant into the receiver

105

Nehéz

What is the role of a suction liquid separator (also in systems with flammable or toxic refrigerants)?


It is used only to measure moisture
It prevents liquid refrigerant from entering the compressor
It heats the refrigerant before the evaporator
It separates liquid from oil

106

Nehéz

What is the function of an oil separator in systems using flammable or toxic refrigerants?


Heats the refrigerant before it enters the evaporator
It prevents liquid from entering the compressor
They are used solely to measure the moisture content of the refrigerant
Separates oil from the refrigerant and facilitates the return of oil to the compressor

107

Közepes

What is the purpose of oil level regulators in a refrigeration system?


They drain off excess refrigerant
They control the evaporator temperature
Maintains the correct oil level in the compressor
They control the pressure in the condenser

108

Közepes

What is the function of the liquid receiver in relation to system tightness?


It controls the evaporating temperature by varying the circulating charge
It keeps the whole system at constant pressure regardless of load
It regulates the oil returning to the compressor
It stores refrigerant; checking its liquid level helps detect charge loss

109

Közepes

What is the role of a gauge manifold with thermometers (temperature probes)?


It controls oil level
It measures pressures and temperatures to determine superheat and subcooling and thus assess the system charge (indirect leak check)
It monitors refrigerant moisture content
It relieves pressure if it is exceeded

110

Közepes

What is the role of defrost controls?


They drain excess oil from the evaporator to the receiver
They control compressor discharge pressure during defrost
They protect the evaporator from icing and damage that could lead to leaks
They monitor the moisture content of the refrigerant

111

Nehéz

Why do liquid and oil separators in CO₂ systems require particular attention?


Because CO₂ is flammable and separators must not be used
Because CO₂ needs no lubrication, so oil separators are unnecessary
Because sight glasses and level indicators must not be used in CO₂ systems
Because of very high pressures – adequate PS and protection devices are required

112

Nehéz

What is the critical pressure of CO₂ (R744)?


Approx. 74 bar (abs)
Approx. 120 bar
Approx. 10 bar
Approx. 31 bar

113

Könnyű

What is the unit of pressure in the International System of Units (SI)?


Pa (pascal)
psi (pound per square inch)
bar (gauge)
atm (standard atmosphere)

114

Közepes

Where can the lists of fluorinated greenhouse gases be found?


In the Vienna Convention for the Protection of the Ozone Layer
In Annexes I–III to Regulation (EU) 2024/573 of the European Parliament and of the Council
In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In a regulation of the Minister of Economy on the list of fluorinated greenhouse gases

115

Nehéz

What characterises the transcritical process in CO₂ systems?


It occurs only at low temperatures
It is irrelevant to system operation
Conventional condensation occurs
Heat rejection takes place above the critical point – the refrigerant does not condense in the conventional way (gas cooler instead of condenser)

116

Nehéz

What characterises the subcritical CO₂ process?


The absence of evaporation
The conventional condensation process below the critical point
The absence of condensation
Operation above the critical point

117

Könnyű

What is the log(p)-h diagram for CO₂ used for?


To detect leaks
To measure temperature
To regulate pressure
For analysing thermodynamic processes in a refrigeration system

118

Könnyű

What can be read from the log(p)-h graph?


Pressure, enthalpy, temperature and state of the refrigerant
Only the amount of refrigerant
Only the temperature
Only the humidity

119

Könnyű

What are CO₂ saturation tables used for?


To determine the relationship between temperature and pressure at saturation
To measure humidity
To regulate the compressor
To determine the oil quantity

120

Könnyű

What does the CO₂ saturation state mean?


A state in which the refrigerant is only a gas
A state of high pressure
Dry ice state
Equilibrium between the liquid and vapour phases

121

Nehéz

When can dry ice (solid CO₂) form?


During normal operation of the system
When the pressure drops suddenly below the triple point (approx. 5.2 bar abs, −56.6 °C), e.g. when venting liquid CO₂ or charging liquid into an evacuated system
At high pressure
At high temperature

122

Nehéz

What risks are associated with dry ice forming in a CO₂ system?


Blocked pipes and valves and system damage (and a sharp pressure rise when it thaws)
Improved efficiency
No risk
Pressure reduction

123

Nehéz

How does CO₂ saturation pressure change as temperature increases?


It increases rapidly
It decreases
It first decreases, then increases
It remains the same

124

Könnyű

Why is understanding the log(p)-h graph particularly important for CO₂?


As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It doesn’t matter
It only applies to NH₃
It is only used for design purposes

125

Közepes

Where can the lists of ozone-depleting substances be found?


In the national Act on ozone-depleting substances and certain fluorinated greenhouse gases
In a regulation of the Minister of the Environment on the list of controlled substances
In the Vienna Convention for the Protection of the Ozone Layer
In Annexes I and II to Regulation (EU) 2024/590 of the European Parliament and of the Council

126

Nehéz

What happens to CO₂ above the critical point?


It transitions to a supercritical state (no distinction between liquid and gas)
It ceases to conduct heat
It turns into a solid
It turns into a liquid

127

Könnyű

Why do CO₂ systems require precise pressure control?


They do not require control
Due to significant pressure changes with temperature fluctuations
Due to low pressures
Because there are no valves

128

Közepes

Why is ammonia (R717) classed as a toxic refrigerant?


Because it is heavier than air and displaces oxygen
Because it does not react with water, making neutralisation difficult
Because it is colourless and odourless and therefore hard to detect
It severely irritates the respiratory tract, eyes and skin, and is poisonous when inhaled at higher concentrations

129

Nehéz

What is the main difference between a dry-expansion and a flooded evaporator?


A dry-expansion evaporator needs no expansion valve, a flooded one does
In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator always has a lower pressure than a flooded one
A dry-expansion evaporator is filled with liquid, a flooded one with vapour

130

Nehéz

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Atmospheric pressure, approx. 1 bar abs
Positive pressure of 5–10 bar
Below atmospheric (approx. 0.7 bar abs at −40 °C)
Positive pressure of 10–20 bar

131

Nehéz

Why are PFAS formed by the decomposition of certain F-gases (e.g. TFA from HFOs) problematic?


They cause rapid cooling of the atmosphere
They are very persistent, accumulate in the environment (e.g. water) and may be toxic
They are climate- and environment-neutral
They are readily biodegradable

132

Könnyű

What is the basic requirement when charging a system with R717 (NH₃)?


Charging must only take place at temperatures below 0°C
NH₃ can be charged together with air
Charging can be carried out without personal protective equipment
Charging should take place in a well-ventilated area using appropriate personal protective equipment

133

Nehéz

How is oil managed in R717 systems?


Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer
Oil can be mixed with any refrigerant
Oil has no effect on system operation
Oil requires no monitoring

134

Könnyű

What is the correct procedure for recovering R717 from a system?


The gas can be released into the atmosphere
Recovery is not required
The refrigerant can be drained into the sewer system
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃

135

Könnyű

How should R717 (NH₃) be stored?


In sealed, labelled containers, in a cool and well-ventilated place
Near heat sources
In unmarked plastic containers
In any open containers

136

Közepes

Where and by when must entities obliged under the Polish Act of 15 May 2015 submit annual reports on ODS and F-gases?


By 28 February of the following year, electronically via the Reports Database (BDS) run at the Institute of Industrial Chemistry (ICHP)
By the end of the calendar year, on a form at a regional office of the Office of Technical Inspection (UDT)
By 31 March, electronically to the Ministry of Climate and Environment
By 31 January, in the Central Register of Operators (CRO)

137

Nehéz

What should be done with contaminated R717?


Dilute it with water and reuse it
Purify it or send it for disposal in accordance with regulations
Release it into the atmosphere
Continue to use it without restriction

138

Könnyű

What is the main hazard associated with an R717 leak during maintenance work?


No risk whatsoever
Damage to electrical equipment only
Toxic to humans and may cause chemical burns
Increased cooling efficiency

139

Nehéz

What should be done if an NH₃ leak is detected?


Carry on working wearing a dust mask
Carry on working with the room door open
Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)
Increase the pressure in the system

140

Nehéz

What role do scrubbers play in NH₃ systems?


They increase the pressure in the system
They are used to measure temperature
They store the refrigerant
Neutralise ammonia through absorption in a liquid (e.g. water)

141

Nehéz

How should the system be prepared before filling with R717?


Simply start it up
The pressure must be increased above the standard level
There is no need to check it
Check for leaks, remove air and moisture, and create a vacuum

142

Nehéz

What are the transport requirements for R717?


Transport is not regulated
It can be carried in open containers
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)
It can be carried without labelling

143

Könnyű

What personal protective equipment is required when working with NH₃?


No requirements
Only a safety helmet
Workwear only
Safety goggles, gloves and respiratory protective equipment

144

Közepes

Which installation measure has a major impact on compressor energy efficiency?


Proper evacuation and dehydration of the system (removing air and moisture)
Charging extra refrigerant 'as a reserve' above the nameplate value
Installing a suction line smaller than recommended
Omitting the filter-drier to reduce flow resistance

145

Közepes

How does regular oil-level monitoring affect compressor operation?


It allows the crankcase heater to be omitted
It increases cooling capacity above nominal
It allows any type of oil to be topped up
It ensures proper lubrication and limits wear and energy losses

146

Könnyű

How do system leaks affect compressor energy efficiency?


Refrigerant loss reduces capacity and increases energy use (longer run times, higher superheat)
They improve efficiency because condensing pressure drops
No effect as long as the system still cools
They affect only safety, not energy use

147

Közepes

Regulation (EU) 2024/590 relates to:


Ozone-depleting substances
Health and safety during refrigerant recovery
Alternative refrigerants replacing fluorinated greenhouse gases
Conditions for F-gas certification of companies recovering and reclaiming refrigerants

148

Közepes

What is the significance of proper suction and discharge pressure control?


The lowest possible suction pressure is best
Pressures do not affect energy use
It keeps the compressor at optimal conditions (suction pressure as high and condensing pressure as low as permissible)
The highest possible condensing pressure is best

149

Közepes

Which maintenance measure reduces compressor energy consumption?


Raising the high-pressure switch setting
Topping up refrigerant at every service visit
Replacing the filter-drier when the pressure drop or moisture indicator shows it is necessary
Permanently disabling the crankcase heater

150

Közepes

How does air (non-condensable gas) in the system affect operation?


It lowers the condensing pressure
It only affects the sight-glass indication
It raises the condensing pressure and reduces efficiency
It improves condenser heat transfer

151

Közepes

What role do controls play in compressor efficiency?


They enable optimised operation and lower energy use (e.g. floating head pressure, capacity matching)
They matter only in NH₃ systems
They increase the circulating refrigerant charge
They provide safety only, with no energy effect

152

Közepes

How does suction superheat at the compressor affect efficiency?


The higher the superheat, the higher the efficiency
Excessive superheat reduces efficiency and raises the discharge temperature
Superheat has no effect
Zero suction superheat is optimal

153

Közepes

How does correct system layout affect efficiency?


It doesn't matter
Longer pipes improve subcooling and always increase efficiency
It affects only appearance
It shortens pipe runs and limits pressure drops and energy losses

154

Közepes

How important is suction pipe insulation?


It increases energy consumption
It is needed only for appearance
It limits heat gain and excessive superheat, improving efficiency
It has no effect

155

Közepes

Which measure most improves condenser energy efficiency?


Regular cleaning of heat-exchange surfaces
Raising the condensing pressure set point
Increasing the refrigerant charge
Reducing fan speed to the minimum

156

Könnyű

How does a dirty condenser affect the operation of the refrigeration system?


It improves efficiency
Causes an increase in pressure and energy consumption by the compressor
It lowers the condensing pressure
It has no effect

157

Könnyű

Why is adequate airflow through an air-cooled condenser important?


It doesn't matter
It affects only noise
The lower the airflow, the lower the condensing pressure
It ensures effective heat rejection and low condensing pressure

158

Közepes

Which refrigerants damage the ozone layer?


All refrigerants containing chlorine or bromine in their molecules
All refrigerants containing carbon in their molecules
All refrigerants containing fluorine and hydrogen in their molecules
All natural refrigerants

159

Könnyű

How does the presence of limescale in a water-cooled condenser affect performance?


It has no effect
Impairs heat exchange and increases energy consumption
It lowers the condensation temperature
It improves heat transfer

160

Közepes

How does correct condensing pressure control affect efficiency?


It keeps the lowest pressure that still ensures proper expansion-valve feed, reducing energy use
It always increases energy use
It has no effect
It is best to keep a constant high condensing pressure all year

161

Könnyű

How do condenser leaks affect energy efficiency?


Causes refrigerant loss and a drop in efficiency
They improve efficiency
Have no effect
They lower the temperature

162

Könnyű

How important is the correct positioning of an air-cooled condenser?


It should be housed in a small room
It doesn’t matter
It should be installed in a well-ventilated area with unobstructed airflow
It should be close to heat sources

163

Könnyű

How does hot air recirculation affect the condenser?


It reduces the pressure
It improves efficiency
It has no effect
Impairs cooling and increases energy consumption

164

Közepes

How does insulation of heating and DHW pipework affect the efficiency of a heat pump system?


It increases pressure
It doesn't matter
It impairs cooling
It reduces energy losses and improves overall system efficiency

165

Közepes

Which measure most improves the energy efficiency of an air-cooling evaporator?


Defrosting at the right time and keeping the fins clean
Increasing the refrigerant charge above nominal
Raising the condensing temperature by a few kelvin
Restricting the airflow through the evaporator

166

Könnyű

How does evaporator icing affect the system’s operation?


It improves cooling performance
It has no effect
Impairs heat exchange and increases energy consumption
It lowers the condensation temperature

167

Könnyű

How does dirt on the evaporator surface affect its performance?


Impairs heat exchange and increases energy consumption
It reduces the pressure
It has no effect
It improves efficiency

168

Könnyű

What maintenance task is crucial for the evaporator?


Regular cleaning and defrosting
Reduced airflow
Increasing the refrigerant charge
Lack of maintenance

169

Közepes

What does a Certificate A2 for natural persons (Implementing Regulation (EU) 2024/2215) authorise?


Only recovery of F-gases from equipment containing less than 3 kg (or 6 kg in hermetically sealed systems)
Only leak checks that do not entail breaking into the refrigerant circuit
All activities (leak checks, installation, repair, maintenance, servicing, decommissioning, recovery) involving F-gases and hydrocarbons in equipment containing less than 3 kg, or less than 6 kg in labelled hermetically sealed systems
All activities involving equipment using CO₂ (R744)

170

Könnyű

How does superheat at the evaporator outlet affect efficiency?


It always improves performance
It has no effect
Excessive superheat reduces energy efficiency
It only causes a temperature drop

171

Könnyű

How do leaks in the evaporator affect efficiency?


Increase capacity
Have no effect
These cause refrigerant loss and a drop in efficiency
Improves performance

172

Könnyű

How important is correct expansion valve adjustment?


It increases energy consumption
It doesn’t matter
Ensures optimal evaporator charge and improves efficiency
Causes leaks

173

Könnyű

How does inadequate insulation of suction (or secondary-coolant) pipes affect evaporator performance?


It lowers the condensing temperature
It improves efficiency
It causes cooling losses and increased energy use
It has no effect

174

Könnyű

How does correct TEV adjustment affect system energy efficiency?


It ensures optimal superheat and improves efficiency
It causes leaks
It has no effect
It increases energy use

175

Könnyű

What happens if the superheat set by the TEV is too high?


The refrigerant charge will increase
It has no effect
Efficiency will drop because the evaporator is not being fully utilised
Cooling efficiency will improve

176

Közepes

How does too low superheat setting on the TEV affect performance?


It reduces refrigerant flow
It has no effect
It increases operational safety
It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid

177

Könnyű

How do contaminants in the system affect the operation of the TEV?


They improve its performance
Have no effect
They can cause it to become blocked and reduce efficiency
They lower the temperature

178

Könnyű

What role does the filter-drier play in terms of system efficiency?


It lowers the temperature
Removes moisture and contaminants, improving the system’s efficiency
It doesn’t matter
It increases the amount of refrigerant

179

Könnyű

How does proper insulation of components (e.g. pipes near the TEV) affect the system?


It increases energy consumption
It doesn’t matter
It causes leaks
Prevents unwanted heat gains and improves efficiency

180

Közepes

What is the scope of Regulation (EU) 2024/573?


Only requirements for periodic leak checks of refrigeration equipment
Limiting emissions, use and marketing of F-gases, HFC phase-down, certification and reporting
Health and safety requirements for brazing and welding on refrigeration installations
Design requirements and conformity assessment for pressure equipment

181

Könnyű

How important is it to check the operation of the condensing pressure control valve in the system?


It has no effect
It increases energy consumption
It causes a significant rise in temperature
Ensures operation within the optimum pressure range and reduces energy losses

182

Könnyű

How does the correct selection of a TEV affect energy efficiency?


It lowers the temperature
It doesn’t matter
Ensures the system is matched to its capacity and operates optimally
It increases the amount of refrigerant

183

Közepes

What is the main design difference in hydrocarbon refrigeration systems?


No need for safety measures
Higher operating pressures
The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability
Lower energy efficiency

184

Közepes

How do compressors used in hydrocarbon systems differ?


They must operate at higher pressures than HFC compressors
There is no difference
They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)
They need no lubrication

185

Nehéz

What is the main characteristic of R744 (CO₂) refrigeration systems?


Low energy efficiency under all conditions
Low operating pressures
No need for control
Very high operating pressures

186

Nehéz

What are the requirements for piping materials in CO₂ systems?


They must withstand high pressures (e.g. stainless steel, high-strength copper-alloy tubes such as K65)
Only plastics
Any material may be used
It doesn't matter

187

Nehéz

How does a booster system work in CO₂ installations?


Low-temperature (LT) compressors discharge into the suction of medium-temperature (MT) compressors – two-stage compression in a single circuit
It reduces evaporator pressure
It is used to store refrigerant
It reduces the refrigerant quantity

188

Könnyű

What is the function of high-pressure control valves in CO₂ systems?


They control the pressure on the high-pressure side and optimise system operation
They lower the evaporator temperature
They regulate oil flow
They are used to store the refrigerant

189

Nehéz

Why is pressure optimisation in CO₂ systems crucial?


It reduces the amount of refrigerant
It reduces the ambient temperature
It enables the system to achieve maximum energy efficiency in transcritical mode
It doesn’t matter

190

Nehéz

What role does parallel compression play in CO₂ systems?


It lowers the ambient temperature
It compresses flash gas from the intermediate receiver directly to high pressure, improving efficiency
It increases energy consumption
It has no significance

191

Közepes

How can you tell that the system has been overcharged with refrigerant?


Under normal operating conditions the condensing pressure and subcooling rise markedly because excess liquid floods the condenser and reduces its active surface
It cannot be checked, because the sight glass is not intended for this
Even under a very small heat load, frost forms on the suction line
The compressor runs at a lower load and the suction pressure drops

192

Nehéz

How does an ejector work in a CO₂ system?


It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
It lowers the evaporator temperature
It increases the amount of refrigerant
Stores the refrigerant

193

Nehéz

What is the function of liquid ejectors in CO₂ systems?


They return liquid from the separator and allow partially flooded evaporator operation (better evaporator feed)
They raise the refrigerant temperature
They reduce atmospheric pressure
They increase the amount of oil

194

Nehéz

What are the characteristics of partially flooded systems in CO₂ systems?


The absence of liquid in the evaporator
Lack of regulation
Low operating pressure
The presence of liquid in the evaporator, which improves heat transfer and efficiency

195

Nehéz

What is the main risk associated with standstill pressure in CO₂ systems?


A drop in temperature
A pressure rise as the refrigerant warms up during standstill (possibly exceeding PS and lifting the relief valves)
Increased efficiency
A decrease in refrigerant quantity

196

Nehéz

How is standstill pressure limited in CO₂ systems?


By increasing the refrigerant charge
By completely shutting down the system and power supply
By using an auxiliary standstill (stagnation) cooling unit, e.g. cooling the receiver, with back-up power, and by selecting an adequate PS and relief valves
By raising the plant-room temperature

197

Nehéz

What does standstill (stagnation) of a CO₂ system mean, and why is it important?


Improved efficiency
A drop in system temperature
A state with no compressor operation or refrigerant flow – pressure rises with ambient temperature and may exceed PS
Normal system operation

198

Könnyű

Why do CO₂ systems require more advanced automation than traditional systems?


Due to low pressures
They do not require automation
Due to the need for precise control of pressure and temperature
Because there are no valves

199

Nehéz

What must the label of a flammable refrigerant cylinder include?


Information about the cylinder owner
The refrigerant name, the UN number, the hazard label (e.g. 2.1 – flammable gas) and basic safety information
Only the refrigerant name
Only the net weight

200

Nehéz

Why is the absence of a 'flammable refrigerant' label on equipment a serious hazard?


It may lead to the wrong oil being selected
It has no significant effect on safety
It reduces system efficiency
It may lead to the use of tools that are ignition sources

201

Nehéz

Which set of information on the label of a flammable refrigerant cylinder is crucial from a safety perspective?


Gross weight and batch number
Manufacturer’s name and country of origin
Name of the substance, hazard label (ADR) / GHS pictogram (CLP), UN number
Cylinder colour and date of manufacture

202

Közepes

Before charging the unit with refrigerant, it is essential to…


…fill in the unit's data sheet
…check the compressor suction and discharge connections
…carry out a tightness test (and evacuate the system)
…carry out a trial start-up

203

Könnyű

What is the requirement regarding the labelling of an installation containing a flammable substance?


The labelling must indicate the type of substance and the flammability hazard
Labelling is not required for hermetically sealed systems
Colour-coding of pipes is sufficient
Labelling is required only in technical rooms

204

Könnyű

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


No impact on safety
Merely a reduction in efficiency
Merely installation difficulties
Risk of leakage and the formation of an explosive mixture

205

Nehéz

What is the purpose of gas detectors in a room with a refrigeration system?


Measuring refrigerant temperature
Controlling compressor capacity
Monitoring pipe pressure
Early leak detection and triggering of measures preventing health risks and explosive atmospheres (alarm, ventilation, shut-off)

206

Nehéz

How often should gas detection sensors in a machinery room be checked?


Only after a leak has occurred
Before every start-up of the unit
Once every 5 years
According to the manufacturer's instructions and regulations – at least every 12 months

207

Nehéz

Where should a gas detector be located according to EN 378?


Only at the room entrance
Where the refrigerant would accumulate: low (near the floor) for refrigerants heavier than air, high (near the ceiling) for lighter ones such as NH₃
Anywhere in the room
Near the control panel

208

Könnyű

How should an employee respond when a gas alarm is triggered?


Switch off the system and wait for the alarm to stop
Reduce the pressure in the system
Leave the room immediately and notify their supervisor
Carry on working until they see a leak

209

Nehéz

What safety checks should be carried out when installing a new refrigeration system with a flammable refrigerant?


The colour of pipes and hoses
Only that the air filter is new
Only the compressor power
The presence of health and safety signage, adequate ventilation and gas detectors

210

Könnyű

Gas detectors should be installed in rooms where:


Ventilation is natural
Any refrigerant is present, regardless of the quantity
The room is less than 5 m²
The amount of refrigerant exceeds a specified permissible threshold

211

Nehéz

What are the requirements for emergency exits from a refrigeration machinery room?


One exit with a sign stating the refrigerant type is sufficient
Outward-opening doors and signed escape routes (number of exits per the standard)
At least two exits are required and signage is optional
In small machinery rooms emergency exits need not be signed

212

Nehéz

Which installation measure for a flammable-refrigerant system improves its energy efficiency?


Restricting room ventilation
Omitting the filter-drier
A thorough tightness test and evacuation (dehydration) of the system
Charging above the nameplate quantity

213

Közepes

What information must appear on the label of equipment containing F-gases?


The weight and capacity of the pipework and the colour code of the casing paint
That it contains an F-gas, its designation, quantity in kg and t CO₂ eq, and GWP
Only the trade name of the refrigerant and the unit's serial number
The manufacturer's logo, the unit weight and year of manufacture from the rating plate

214

Könnyű

How do leaks affect systems using flammable refrigerants?


They improve efficiency
Have no effect
They cause refrigerant loss, reduced efficiency and a fire hazard
They lower the temperature

215

Nehéz

Why is it important to limit the refrigerant charge in HC systems?


It increases capacity
It limits the possibility of reaching a flammable concentration (≥ LFL) in a leak, increasing safety
It lowers the temperature
It doesn't matter

216

Könnyű

Why is the cleanliness of heat exchangers in HC systems important?


Causes leaks
It doesn’t matter
It increases the pressure
It improves heat transfer and reduces energy consumption

217

Könnyű

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Lack of servicing
Regular checks for leaks and operating parameters
Disabling safety devices
Increasing the refrigerant charge

218

Könnyű

How does the correct selection of components affect a system using a flammable refrigerant?


It ensures safe and optimal operation and minimises energy losses
It doesn’t matter
It lowers the temperature
It increases the amount of refrigerant

219

Könnyű

Why is it important to use the correct service tools in HC systems?


It increases energy consumption
Causes leaks
It ensures operational safety and reduces refrigerant losses
It doesn’t matter

220

Könnyű

How does pipe insulation affect the efficiency of systems containing HC?


It increases the pressure
It reduces energy losses and improves efficiency
It doesn’t matter
Causes leaks

221

Nehéz

Which safety class applies to R744?


A1
A2.
A3
B2L

222

Nehéz

In a simple single-stage R744 system without an intermediate receiver (refrigerant flows from the gas cooler directly to the expansion valve), operating transcritically at 90 bar with a gas-cooler outlet temperature of 35 °C, the refrigerant upstream of the expansion valve is…


…a supercritical fluid
…saturated vapour at intermediate pressure
…a two-phase mixture at intermediate pressure
…a subcooled liquid

223

Nehéz

In R744 transcritical systems, the gas cooler outlet valve controls:


The outlet temperature of the gas cooler
The inlet temperature to the gas cooler
The gas cooler fans
The pressure in the gas cooler

224

Könnyű

What is the base unit of temperature according to the International System of Units (Système International d’Unités)?


K
°C
°F
°R

225

Közepes

Which set of information best reflects the content of the equipment records required by Regulation (EU) 2024/573?


The make and model of the unit
The owner, installer and service technician of the unit
Only the date of installation and the installer's name
Operator details, equipment details, type and quantity of refrigerant, and information on servicing and repairs

226

Nehéz

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 does not mix with the oil; the oil collects on the high-pressure side above the R717
An oil return line cannot be used in R717 systems because the oil is too hot
R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)

227

Nehéz

What is the main reason for using K65 copper tubing in some R744 systems?


They can withstand higher pressures
They have good low-temperature performance
They come in a wider range of diameters
They bend easily

228

Nehéz

Which statement about installing Schrader valves is correct?


Hydrocarbons leak through Schrader valves
All Schrader cores are suitable for all refrigerants
Schrader valves must not be used in R744 systems
When brazing the valve body, the core must be removed, then refitted and tightened to the correct torque

229

Nehéz

Which refrigerant can be detected with phenolphthalein paper?


R717
R1270
R744
R1234ze(E)

230

Nehéz

How does an undercharge affect the high-pressure side (without discharge pressure control)?


Discharge (condensing) pressure and subcooling will both be lower
Discharge pressure higher, subcooling higher
Discharge pressure lower, subcooling higher
Discharge pressure higher, subcooling lower

231

Nehéz

What is the benefit of adding helium as a tracer gas to nitrogen in a pressure test?


Its small atoms pass easily through leaks and are detected
It reacts with refrigerant residues, producing a visible colour change
It has a distinctive odour that helps locate the leak
It has a higher pressure than pure nitrogen in the same cylinder

232

Nehéz

Why should an evacuated R744 system initially be charged with refrigerant in the vapour phase?


To prevent the drain valve on the receiver from opening
To charge R744 more slowly and measure it more accurately
To avoid damaging the compressor with liquid CO₂
To prevent dry ice forming (until approx. 5.2 bar abs is exceeded)

233

Nehéz

If moisture remains in an R744 system because it was not properly evacuated (dehydrated), what is the likely consequence?


Formation of hydrogen fluoride and hydrofluoric acid
Reduced cooling capacity
Excessive discharge pressure
Formation of carbonic acid, which damages the system

234

Nehéz

Which system may require manual oil recovery?


R744 cascade system
An R717 system
Supercritical ‘booster’ system using R744
Secondary system using R744

235

Nehéz

The pressure of R744 at a saturation temperature of 20 °C is approx.


56 bar g
14 bar g
90 bar g
25 bar g

236

Közepes

Who is responsible for keeping the equipment records?


There is no such obligation.
The equipment maintenance technician.
The operator of the unit or system.
The person responsible for risk assessment.

237

Nehéz

Which refrigerant is lighter than air?


R717
R744
R1234ze(E)
R1270

238

Nehéz

What hazards are associated with a safety group A3 refrigerant?


Lower toxicity, no flame propagation
Lower flammability, lower toxicity
Higher toxicity, no flame propagation
Higher flammability, lower toxicity

239

Nehéz

What is the GWP of R32 (per AR4, as used in Regulation (EU) 2024/573)?


675
6
0
3922

240

Nehéz

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Lower flammability limit, height of the indoor unit, floor area
Practical limit, room volume
Practical limit, height of the indoor unit, floor area
Lower flammability limit, room volume

241

Nehéz

What compressor displacement is required for R1270 compared with an R404A compressor in the medium-temperature range (cold room)?


About half
About 1.5 times larger
Similar
About 6 times larger

242

Nehéz

At an ambient temperature of 25 °C, the standstill pressure in the low-pressure stage of an R744 cascade (without standstill cooling) will typically be…


…approx. 27.5 bar g
…the same as the relief valve set pressure
…the same as the high-pressure switch setting
…higher than the maximum allowable pressure (PS) of the low-pressure stage

243

Nehéz

What is the correct definition of critical temperature?


The temperature at which a substance changes from a gaseous to a solid state
The temperature above which there are no distinct liquid and gaseous phases
The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which, for certain substances, electrical resistance is zero

244

Nehéz

In the gas cooler of a transcritical system, the supercritical working fluid…


…rejects heat as its pressure falls
…rejects heat at constant temperature and pressure
…rejects heat as its temperature falls
…rejects heat during a phase change

245

Nehéz

R717 is highly corrosive to:


copper (and its alloys)
aluminium
stainless steel
titanium

246

Nehéz

What can be the effect of a relief valve lifting repeatedly?


The valve may not reseat tightly and its set (opening) pressure may decrease
The set pressure increases
The valve stays fully open permanently
The valve no longer opens

247

Közepes

Where are oil traps installed on the suction line?


At the inlet to every component of the refrigeration system
Before the safety valve on the suction side
Immediately before the compressor suction connection
At the bottom of vertical suction risers with upward flow

248

Nehéz

What is the relationship between the pressure (p) and temperature (T) of nitrogen at the start (1) and end (2) of a tightness test (p absolute, T in kelvin)?


p₂ = T₁/(p₁ × T₂)
p₂ = (p₁ × T₂)/T₁
p₂ = T₂/(p₁ × T₁)
p₂ = (p₁ × T₁)/T₂

249

Nehéz

What is the recommended pre-alarm level for fixed leak detection systems for R717?


500 ppm
5,000 ppm
50,000 ppm
500,000 ppm

250

Nehéz

Why are compressors with a separate motor (open type) mostly used in R717 systems?


To increase the refrigerant charge
Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
To lower the condensing pressure
Because they are cheaper

251

Nehéz

Which type of compressor is most commonly used in large ammonia systems?


Rotary vane compressor
Hermetic scroll
Diaphragm compressor
A reciprocating or screw compressor

252

Nehéz

How is the capacity of a piston compressor regulated in NH₃ systems?


By unloading the cylinders or changing the rotational speed
Solely by adjusting the oil volume
By increasing the condensing pressure
By reducing the refrigerant charge

253

Nehéz

How is the capacity of a screw compressor most commonly controlled?


By changing the type of oil
By closing the suction valve
By adjusting the oil level
By using a slide valve

254

Nehéz

When is two-stage compression used in NH₃ systems?


At low evaporating temperatures (pressures) and high pressure ratios
Only with water-cooled condensers
Only in small systems
At small temperature differences

255

Nehéz

What is the advantage of two-stage compression over single-stage compression?


Lower efficiency
Higher energy consumption
No need for a separator
Higher efficiency and lower discharge temperature

256

Nehéz

How does an evaporative condenser used in NH₃ systems work?


It utilises the evaporation of water to increase cooling efficiency
It transfers heat only to the air
Operates without a fan
It does not require a water supply

257

Nehéz

What is the function of the liquid separator in an NH₃ system?


Increases the discharge temperature
It separates oil from the refrigerant
Regulates the condensing pressure
It prevents liquid from entering the compressor

258

Közepes

Which symptoms with the compressor running indicate a refrigerant leak (undercharge)?


Sight glass full of liquid and rising oil level in the crankcase
Low suction pressure, high superheat and negligible subcooling
Rising liquid level in the receiver and increasing subcooling
Rising condensing and suction pressures with no superheat

259

Nehéz

What is the purpose of monitoring the liquid level in the separator?


To reduce the condensing temperature
To control the condenser fan
To increase the oil volume
To maintain the correct refrigerant level and prevent the compressor from flooding

260

Nehéz

What is the role of the float switch in NH₃ systems?


It regulates the condensation temperature
It is used to detect leaks
It monitors the liquid level in the tank or separator
It controls the fan’s operation

261

Nehéz

What is a thermosyphon in NH₃ systems?


A type of safety valve
An oil circulation pump
A defrosting device
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling

262

Nehéz

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To reduce the pressure
To increase the amount of refrigerant
Because the oil mixes only with water
Because NH₃ does not mix with most compressor oils

263

Nehéz

What is the main function of an oil separator in NH₃ systems?


To lower the condensation temperature
To increase fan efficiency
Removing moisture from the system
To separate the oil from the refrigerant and return the oil to the compressor

264

Nehéz

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


A pumped liquid-recirculation system
A glycol system
An indirect system
A direct-expansion (DX) system

265

Nehéz

What is the characteristic feature of a flooded evaporator system?


The evaporator contains a large amount of liquid, which improves heat transfer
No level control is required
No separator is used
The evaporator is filled exclusively with vapour

266

Nehéz

What is the main difference between a direct and an indirect system?


In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, no compressor is used
In a direct system, there is no evaporator
In an indirect system, NH₃ flows directly into the space being cooled

267

Közepes

Which components of a refrigeration system are potential leak points subject to leak checks?


Only suction-side components
Joints, valves (including stems), seals (including those on replaceable filters and driers), parts subject to vibration and connections to safety and measuring devices
Hermetic compressors, liquid receivers and liquid separators
Only high-pressure-side components

268

Közepes

What pressure is used for the pressure tightness test of an installation?


A pressure chosen by the technician based on experience
Always 30 bar
A pressure equal to the maximum pressure measured during operation
The pressure specified in EN 378-2 or by the manufacturer, not exceeding the maximum allowable pressure of the system (PS)

269

Közepes

At which points of the unit must the leak check be carried out?


Only at connections of measuring instruments
Only on discharge-side components
At all points where there is a potential risk of refrigerant leakage
Only on compressor shut-off valves, solenoid valves and filters

270

Közepes

When can a unit be considered tight after a pressure test?


When gas bubbles appear after immersion in water
When the pressure drop does not exceed 0.1 bar regardless of the test duration
When the pressure remains constant during the test (allowing for temperature-related changes); any unexplained pressure drop requires the leak to be located
When it has been checked with a fixed electronic detector

271

Közepes

Which legal act currently sets out the obligation to check stationary refrigeration equipment containing F-gases for leaks, and how often this must be done?


Regulation (EU) No 517/2014
Implementing Regulation (EU) 2024/2215
Regulation (EU) 2024/573
Commission Regulation (EC) No 1516/2007

272

Nehéz

Which parts of a refrigeration system should be given particular attention during a leak check?


Compressor and receiver connections, because the pressure is highest there
Only condenser connections, because the refrigerant is liquid there
Only compressor connections, because they are the only parts subject to vibration
Joints, valves incl. stems, seals, parts subject to vibration, connections to safety devices

273

Könnyű

What is the superheat of refrigerant vapour?


The difference between the actual vapour temperature and the saturation temperature corresponding to its pressure (expressed in K)
The difference between the saturation temperature and the actual liquid temperature in the liquid line
The difference between the condensing temperature and the ambient temperature
The amount of heat required to evaporate a liquid

274

Nehéz

Leak checks can be carried out using various methods. Which pair is correct?


Material quality control methods and electronic methods
Direct and indirect methods
Physical and chemical methods
Methods with and without quality control of supplies

275

Nehéz

To whom can leak checks of stationary refrigeration equipment containing F-gases be entrusted?


A person who has carried out such checks before
Any leak-testing specialist
A natural person holding a certificate covering leak checks (A1, A2 within its charge limit, or E)
An employee appointed by the owner of the installation

276

Nehéz

What conditions must be met to use UV dye for leak checking?


Manufacturer approval of the method and a certificate covering breaking into the circuit
It is sufficient that introducing dye into the circuit is technically feasible
A UDT authorisation for pressure testing is required
It is sufficient to have a UV lamp, dye and safety goggles

277

Nehéz

Which leak-checking methods are considered direct methods?


Pressure-change measurement and immersion in water
Vacuum test and foam solution
Nitrogen with tracer gas and pressure measurement
1. gas detection devices (portable or fixed leak detection system), 2. UV detection fluid or dye, 3. bubble/foam solutions

278

Nehéz

What do indirect leak-checking methods involve?


Leak detection with UV dye
Leak detection with an electronic detector
Ultrasonic measurement
A visual and manual check and analysis of parameters: pressure, temperature, compressor current, liquid levels and recharge volume

279

Közepes

How should the pressure be increased during a pressure tightness test?


As quickly as possible
Gradually, in stages, checking for leaks at each level until the test pressure is reached
In one step, by fully opening the nitrogen cylinder valve
In any way

280

Közepes

What electronic equipment should be used for leak checking?


Only hot-cathode devices
Only devices with an 'ion pump' sensor
Only detectors with an infrared sensor
Detectors suited to the refrigerant in the system, with appropriate sensitivity, checked periodically

281

Közepes

What documentation should be checked before starting a leak check?


Only the installation invoice and the first start-up report
The equipment records – especially recurring problems and previous leaks
Attendance sheets of the plant-room staff for the year
The operator's fixed-asset inventory ledger

282

Közepes

What information must be recorded in the leak check report?


Date, number and location of leaks, how they were repaired, technician details and signature
The date, a general note about the leak and the operator's signature
The method used, the time spent on site and the cost of repair
Only the number of leaks found and the date of the check

283

Közepes

What pressure should be used for the pressure tightness test?


Always 2–3 bar
Always 10–12 bar
A pressure not exceeding the maximum allowable pressure of the system (PS)
Any pressure, at the technician's discretion

284

Közepes

What is the temperature glide of a refrigerant?


The temperature drop of the refrigerant across the expansion valve
The temperature rise of the vapour in the compressor
A property of single-component refrigerants, for which one saturation temperature corresponds to a given pressure
In zeotropic mixtures, the difference between the temperatures at the start and end of a phase change (boiling or condensation) at constant pressure

285

Nehéz

What does a vacuum (decay) test involve?


After isolating the pump, you check whether the system pressure rises
The pump is restarted every time the system pressure rises
The pump runs continuously to hold the required vacuum for the test
With the pump running, you watch the vacuum gauge reading

286

Nehéz

How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?


On initial commissioning.
Once every six months.
At least once every 12 months.
Only when servicing the unit.

287

Nehéz

How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?


At least once every 12 months.
On initial commissioning.
Once every six months.
Only when servicing the unit.

288

Közepes

In which equipment is a leakage detection system required?


Equipment with 5 t CO₂ eq or more of F-gases, regardless of equipment type
Equipment with 30 kg or more of F-gases, regardless of their GWP
Equipment with ≥ 500 t CO₂ eq of Annex I F-gases (or ≥ 100 kg of Annex II Section 1 gases)
Equipment with 50 t CO₂ eq or more of F-gases, regardless of equipment type

289

Nehéz

Under Regulation (EU) 2024/573, a leakage detection system is mandatory when:


the equipment contains a flammable refrigerant in any quantity
the F-gas charge of the refrigeration equipment is 500 t CO₂ eq or more
the equipment operates in an enclosed space
the charge is 100 kg or more of ozone-depleting substances

290

Nehéz

Which leak-checking method may NOT be used by a holder of a Category E certificate?


Leak checking with a fluorescent dye introduced into the circuit
Checking with a foaming solution
Visual inspection
Measurement with a handheld electronic detector

291

Közepes

What should you check before using a portable electronic leak detector?


That it has an infrared sensor, as only this type is permitted
That it has been zeroed close to the suspected leak point
That it holds a valid UDT inspection certificate
That it suits the refrigerant and has been checked as the manufacturer requires

292

Közepes

Which certificate types (A1, A2, B, C, D, E) authorise leak checks of equipment containing F-gases?


A1, A2 and E
Only E
All except D
Only A1 and A2

293

Nehéz

Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?


At any time.
At the next periodic inspection.
Between 24 hours and 1 month after the repair.
Immediately after the repair.

294

Nehéz

How often must refrigeration equipment containing ≥500 t CO₂ eq of F-gases be checked if (contrary to Article 6) no leakage detection system is installed?


Every 3 months
Every month
Every 6 months
Every 12 months

295

Közepes

Why is it advisable to subcool the liquid refrigerant?


To allow a condenser with a smaller heat-exchange surface to be used
To allow a smaller expansion valve to be used
To lower the evaporating temperature in the evaporator
To ensure that liquid free of vapour bubbles enters the expansion valve

296

Közepes

What must be done after repairing a leak in the refrigeration unit of a refrigerated trailer?


Charge an alternative refrigerant, start up and measure the parameters
Issue the invoice and leave the leak check to the next periodic service
Visually inspect only the bolted and brazed joints near the repair
Update the equipment records and carry out a leak check (it may be done directly after repair)

297

Közepes

Recovery of fluorinated greenhouse gases means:


The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases.
The reuse of fluorinated greenhouse gases following a basic purification process.
The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties.
The collection and storage of fluorinated greenhouse gases from containers, products and equipment during maintenance or servicing or prior to their disposal.

298

Közepes

Who is authorised to recover refrigerant from stationary refrigeration equipment containing F-gases?


The administrator of the operator's account in the register
The owner of the installation
A natural person holding a certificate of the relevant type (A1; A2. or D within their charge limit)
The operator

299

Közepes

How must recovered refrigerants be stored?


In a labelled recovery cylinder with a dual valve and a valid inspection
In any used refrigerant cylinder, provided it is leak-tight
In a disposable (non-refillable) cylinder that held the same refrigerant
In any pressure vessel that has some form of approval

300

Közepes

When should the recovery of fluorinated greenhouse gases be carried out:


Always during servicing and maintenance of equipment.
Before the final disposal of equipment and, where applicable, during its servicing and maintenance.
Before each leak test of the equipment.
Only prior to the final disposal of equipment.

301

Közepes

What should be done if recovered refrigerant is contaminated (e.g. with acid, air or moisture)?


Add a special contaminant neutraliser
Hand it over to a specialised, authorised company for reclamation or destruction
Clean the mixture yourself using a filter-drier
Pass it through a particle filter and reuse it

302

Közepes

What should be done if different refrigerants have been mixed in a storage cylinder?


Add a special refrigerant to the mixture
Pass it through a filter-drier and reuse it
Separate the mixture into its components yourself
Hand the mixture over to an authorised company – as a rule for destruction

303

Közepes

How does push-pull refrigerant recovery work?


The recovery unit draws vapour from the recovery cylinder and pushes it into the system; the pressure difference forces liquid refrigerant out of the system into the cylinder
Refrigerant is drawn alternately from the suction and discharge sides of the compressor
Nitrogen is injected into the system, pushing the refrigerant into the atmosphere
The recovery unit draws vapour from the system and condenses it in the cylinder

304

Közepes

What are the options for managing waste refrigerant?


Recycling, reclamation, destruction
Reclamation, recovery
Recovery, disposal
Disposal, storage

305

Közepes

Which management option restores recovered refrigerant to a quality equivalent to virgin product, so that it can be used by any undertaking?


Recycling
Destruction
Storage
Reclamation

306

Közepes

The lower the evaporating temperature, …


…the greater the density of the suction vapour and the lower the refrigerant mass flow rate
…the lower the density of the suction vapour and the lower the refrigerant mass flow rate
…the greater the density of the suction vapour and the greater the refrigerant mass flow rate
…the lower the density of the suction vapour and the greater the cooling capacity of the compressor

307

Közepes

How must transportable pressure vessels (e.g. refrigerant cylinders) be marked?


With the manufacturer's logo and date of manufacture
Among other things: the number of the design and testing standard, marks of the approving country and the inspection body, the date of the initial inspection, and the manufacturer's and operational marks
Only with weight and capacity marks
The marking is optional

308

Közepes

The recovery of refrigerants does not require the use of:


Hoses with shut-off valves.
A refrigerant recovery station.
An electronic leak detector.
Scales with a measurement range suitable for the size of the cylinder being filled.

309

Közepes

What functions does the compressor perform in a refrigeration system?


The compressor creates a vacuum on the suction side of the system
The compressor condenses the refrigerant.
The compressor compresses ambient air and increases the pressure of the refrigerant.
The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure.

310

Könnyű

What is the compression ratio of a compressor?


The ratio of discharge pressure to the effective capacity of the compressor (p/Vk)
The ratio of absolute discharge pressure to absolute suction pressure (pc/po)
The amount of refrigerant compressed per cycle relative to heat capacity
The ratio of suction pressure to discharge pressure (po/pc)

311

Közepes

What is compressor flooding (liquid slugging)?


A large amount of liquid refrigerant in a flooded evaporator, which is a normal operating condition
Flooding of the compressor by rainwater
Liquid refrigerant or oil entering the compression chamber
Excess oil in the condenser

312

Közepes

Within what range is the compressor motor speed typically controlled using a frequency inverter?


By a maximum of 10%
Speed control does not change the cooling capacity
Approximately 30 to 75 Hz, corresponding to about 60–150% of nominal capacity (depending on the compressor manufacturer)
From approximately 10% to 90% of nominal capacity

313

Könnyű

What is the theoretical displacement (swept volume flow) of a compressor?


The volume of vapour drawn in per unit of time, determined by the compressor's geometry and speed (stated by the manufacturer, e.g. in m³/h)
The volume of a single cylinder in cm³
The volume of refrigerant flowing in one piston cycle under actual operating conditions
A value expressed by the coefficient of performance (COP)

314

Közepes

Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?


Because this type of compressor has difficulty starting up if the phase sequence is changed.
Because these types of compressors are sensitive to voltage drops.
Because the motor speed would decrease, and consequently the compressor’s capacity.
Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors.

315

Közepes

What compression ratio should each stage of a two-stage vapour-compression system have (rule of thumb)?


Equal to 1
Greater than 10
Greater than 18
Less than approximately 8

316

Közepes

Why is a shaft seal necessary in open-type compressors?


To prevent air from entering and refrigerant from leaking out of the compressor
To protect the crankshaft bearing
Only to prevent oil leakage
To ensure the bearing remains lubricated

317

Közepes

How can you check whether the liquid refrigerant is sufficiently subcooled?


Check by touch whether the condenser outlet is noticeably colder than ambient
Check whether the whole evaporator surface is covered with an even layer of frost
Check whether the liquid distributor upstream of the evaporator feels warm
Compare the liquid-line temperature with the saturation temperature at the measured condensing pressure

318

Közepes

Why is the compressor crankcase heated?


To limit refrigerant migration into, and dissolution in, the oil during standstill
To dehydrate the oil
To increase dissolution of refrigerant in the oil and improve its viscosity
To keep the lubricating oil liquid

319

Könnyű

What is the clearance (dead) volume of a reciprocating compressor?


The volume between the valve plate and the piston at bottom dead centre
The space between the side of the piston and the cylinder
The volume between the valve plate and the piston crown at top dead centre
The space between the underside of the piston and the crankcase cover

320

Közepes

What are compressor packs (racks)?


Sets of compressors connected in any configuration
Several air-cooled condensers
Several compressors connected in parallel on a common frame with common suction and discharge headers
Units with two-stage compressors

321

Közepes

What is the main advantage of multi-compressor packs?


Stepwise capacity matching to demand, plus redundancy
No need for compressor controls and safety devices
Low purchase cost and easy installation without special controls
A smaller refrigerant charge than a single-compressor system

322

Közepes

What is meant by the operating envelope (application range) of a compressor?


A range determined by the evaporating temperature at a given ambient temperature
The capacity, refrigerant type and dimensions of the compressor
A range determined only by the evaporating temperature
The permissible range of evaporating and condensing temperatures (to, tk), or the corresponding pressures, within which the compressor may operate

323

Közepes

What are the basic functions of oil in a compressor?


Lubricating bearings and sliding surfaces, removing heat, and sealing clearances (e.g. between piston and cylinder, or rotors)
Increasing the cooling capacity of the refrigerant
Absorbing moisture from the refrigerant
Sealing leaks that develop in the installation

324

Közepes

What are the most effective ways of controlling compressor cooling capacity?


Partially covering the evaporator
An expansion valve
Pressure control valves
Changing the displacement: varying the rotational speed or unloading cylinders

325

Közepes

What does hot-gas bypass capacity control involve?


The compressor speed is varied
High-pressure liquid is injected into the suction to increase capacity
Bypass is not used for capacity control
Part of the hot discharge gas is passed through a bypass valve to the suction side (or evaporator inlet), reducing the effective capacity

326

Közepes

What is the fundamental difference between hermetic and semi-hermetic compressors?


The semi-hermetic compressor has no motor inside the casing
The semi-hermetic casing is bolted (can be opened); the hermetic one is welded
Both can be dismantled; they differ only in cooling capacity
Semi-hermetic compressors run more quietly as a complete unit

327

Közepes

How does a scroll compressor work?


It is a positive-displacement compressor in which compression results from the interaction of a fixed and an orbiting scroll.
It uses two screws to compress the refrigerant.
A scroll compressor is also known as a turbo compressor.
It is a type of piston-type device.

328

Közepes

What physical process takes place in the evaporator?


The secondary fluid (glycol, water) evaporates while the refrigerant condenses
The refrigerant condenses
The refrigerant is subcooled as a liquid
The liquid refrigerant evaporates, absorbing heat, and the vapour is slightly superheated at the outlet

329

Közepes

What is the purpose of compressor capacity control?


To ensure compressor lubrication
To match the cooling capacity to the current demand
To match capacity to the condensing temperature
To increase the condensing pressure

330

Közepes

Why is inverter speed control advantageous for refrigeration compressors?


It can be used with any compressor to ensure lubrication
It enables continuous, smooth control of cooling capacity
It increases compressor capacity above nominal at any frequency
Reducing the speed improves oil return to the compressor

331

Közepes

Does the suction gas temperature affect the cooling capacity of the compressor?


Yes, but only if the suction gas is deeply cooled
Yes – higher temperature lowers vapour density, mass flow and capacity
Yes, but only in reciprocating compressors, not scroll
No – capacity depends only on the compressor displacement

332

Közepes

In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?


Only scroll compressors.
No.
Only screw compressors.
Yes.

333

Közepes

What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?


The compressor compresses ambient air and increases the pressure of the refrigerant.
This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running.
This compressor condenses the refrigerant whilst the vehicle is in motion.
This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off.

334

Közepes

Which media most commonly absorb heat from the refrigerant in the condenser?


Ammonia
Only a water–glycol mixture
Air or water
Air and CO₂

335

Közepes

What is the function of the condenser in refrigeration systems?


Absorption of heat rejected in the regenerative heat exchanger
Releasing only the heat absorbed in the evaporator into the surroundings
Releasing to the environment the heat absorbed in the evaporator and the heat added during compression
Releasing only the heat from the compressor into the surroundings

336

Közepes

If the refrigerant temperature on the high-pressure side is above its critical temperature, condensation…


…always occurs regardless of temperature
…does not occur
…occurs provided a special condenser is used
…does not depend on temperature

337

Közepes

How is liquid subcooling usually achieved in a refrigeration system?


By dissolving the refrigerant in oil
In the final section of the condenser (or in an additional subcooler)
With hot high-pressure vapour
With an additional heat exchanger using liquid nitrogen

338

Közepes

What is the purpose of condenser fan speed control?


Only to protect against exceeding the maximum condensing pressure
To reduce energy efficiency
To disperse refrigerant in the event of a leak
To keep the condensing pressure at the correct level

339

Közepes

Which international agreement introduced the global phase-down of HFC production and consumption?


The Kyoto Protocol
The Paris Agreement
The Kigali Amendment to the Montreal Protocol
The Vienna Convention for the Protection of the Ozone Layer

340

Közepes

Which international treaty governs the phase-out of ozone-depleting substances (CFCs, HCFCs)?


The Montreal Protocol
The Stockholm Convention
The UN Framework Convention on Climate Change (UNFCCC)
The Paris Agreement

341

Nehéz

What is the basis of the GWP values in Regulation (EU) 2024/573?


AR6 for all substances
AR4 for all substances
For HFCs (Annex I) – mainly the IPCC Fourth Assessment Report (AR4); for HFOs and non-fluorinated substances (Annexes II and VI) – the Sixth Assessment Report (AR6)
Each Member State sets its own GWP values

342

Nehéz

An air conditioner (not hermetically sealed) contains 2.5 kg of R410A (GWP 2088). How often must it be checked for leaks?


No checks required (below 3 kg)
Every 6 months
Every 3 months
At least every 12 months (5.22 t CO₂ eq)

343

Nehéz

When is labelled hermetically sealed equipment containing HFCs (Annex I) exempt from leak checks?


When it contains less than 10 t CO₂ eq, and in residential buildings also when it contains less than 3 kg of F-gases
Never – hermetically sealed equipment is always checked
When it contains less than 5 t CO₂ eq
Always, regardless of charge

344

Nehéz

Is a chiller containing 50 kg of R1234ze(E) subject to leak checks under Regulation (EU) 2024/573?


Yes – at least every 6 months (every 12 months with a leakage detection system)
No – the threshold is 5 t CO₂ eq and 50 kg of R1234ze is below 1 t CO₂ eq
No – HFOs are not subject to leak checks
Yes – every 12 months, because its GWP is low

345

Nehéz

In 2026, may an existing refrigeration installation using R404A (GWP 3922) be topped up with virgin refrigerant?


Yes – the ban applies only to equipment ≥40 t CO₂ eq
No – only reclaimed or recycled R404A is allowed (until 1 January 2030)
Yes, if the equipment has a leakage detection system
Yes – bans apply only to new equipment

346

Nehéz

After 1 January 2026, may an R410A (GWP 2088) air conditioner be serviced using virgin R410A?


No – the ban covers all HFCs
Yes – the servicing ban for air conditioners and heat pumps covers F-gases with GWP ≥ 2500
No – the ban covers all refrigerants with GWP ≥ 750
Only with reclaimed refrigerant

347

Közepes

Can HFC refrigerant recovered during a repair be put straight back into the same equipment without any cleaning (filtering/drying)?


Yes, if less than 24 hours have passed
Yes, if the operator agrees
Yes, always
No – recovered F-gas may be used for filling only after it has been recycled or reclaimed

348

Közepes

Who may purchase HFCs for servicing refrigeration equipment?


Any business
Any adult
Only a person holding the relevant certificate or an undertaking employing such persons
Only the equipment operator

349

Közepes

Under what condition may non-hermetically sealed split air conditioning charged with F-gas be sold to an end user?


When evidence is provided that installation will be carried out by a certified undertaking
When the user signs a statement that they will install it themselves
Unconditionally
Only if the unit contains less than 3 kg of refrigerant

350

Közepes

By when must the holder of an F-gas certificate issued under Regulation (EU) No 517/2014 first complete refresher training or an evaluation process?


Never – the certificate is valid indefinitely
By 12 March 2029 (and then at least every 7 years)
By 12 March 2025
By 31 December 2030

351

Közepes

What must the holder of a Category I certificate (Regulation 2015/2067) do to continue using it?


Update their knowledge and skills to the level of Certificate A1 (Annex I to Regulation 2024/2215)
Nothing – Category I automatically becomes A1
Update their knowledge to the level of Certificate E
Apply for an extension without training

352

Közepes

What does Certificate C under Implementing Regulation (EU) 2024/2215 authorise?


All activities in Article 2(1) in relation to ammonia (NH₃)
Leak checks without breaking into the circuit
All activities in relation to CO₂
Recovery of F-gases from equipment <3 kg

353

Közepes

May a person enrolled in a certification training course carry out certified activities?


Yes – under the supervision of a certified person, for no more than 24 months in total
Yes – independently, for 6 months
No, never
Yes – with no time limit, if employed by a certified company

354

Közepes

How long must the operator keep the records of equipment subject to leak checks, if they are not kept in a national database?


At least 1 year
At least 2 years
At least 5 years
Until the equipment is decommissioned

355

Nehéz

Since 1 January 2025, may a new single-split air conditioner containing 1.5 kg of R410A be placed on the market?


Yes – the ban applies from 2029
Yes – the ban applies only to units >12 kW
No – single splits <3 kg with F-gases of GWP ≥ 750 are banned
Yes, if the unit is hermetically sealed

356

Nehéz

From when is it prohibited to place on the market split air-to-air systems up to 12 kW containing F-gases with GWP ≥150 (unless required for safety)?


From 1 January 2029
From 1 January 2025
From 1 January 2035
From 1 January 2027

357

Nehéz

Which persistent atmospheric degradation product of R1234yf is classed as a PFAS?


Ozone
Carbonic acid
Trifluoroacetic acid (TFA)
Carbon dioxide

358

Közepes

What distinguishes class 2L refrigerants from class 2?


Higher toxicity
No lower flammability limit
A maximum burning velocity of no more than 10 cm/s
Heat of combustion above 19 MJ/kg

359

Közepes

What is the lower flammability limit (LFL) of propane R290?


Approx. 0.038 kg/m³ (approx. 2.1% by volume)
Approx. 1.8 kg/m³
Approx. 0.307 kg/m³
Approx. 0.38 kg/m³

360

Nehéz

What is the maximum R290 charge per circuit of a commercial refrigerating appliance (e.g. a cabinet) according to EN IEC 60335-2-89:2022?


1.2 kg
150 g
13 × LFL ≈ 494 g
1.5 kg

361

Nehéz

Calculate the maximum R32 charge (LFL = 0.307 kg/m³) for a wall-mounted air conditioner (h₀ = 1.8 m) in a 20 m² room using m_max = 2.5 × LFL^1.25 × h₀ × A^0.5.


approx. 4.6 kg
approx. 13.8 kg
approx. 1.5 kg
approx. 0.46 kg

362

Közepes

Equipment marked 'Ex II 3G' may be used in zone:


1
2 (explosive gas atmosphere unlikely and short-lived)
20 (dusts)
0

363

Közepes

How is explosion hazard zone 2 defined?


An explosive atmosphere is present continuously or for long periods
An explosive atmosphere is likely to occur in normal operation
An area where flammable refrigerants are never used
An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period

364

Közepes

Under which UN number is propane (R290) carried under ADR?


UN 1978
UN 1005
UN 3252
UN 3337

365

Nehéz

What is the maximum quantity of R290 (class 2, group F) that may be carried per transport unit under the ADR 1.1.3.6 exemption?


333 kg
1000 kg
20 kg
Unlimited

366

Közepes

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


At 100% of LFL
At 5% propane by volume
No higher than 25% of LFL
At 150% of LFL

367

Közepes

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


Partly fill it with nitrogen to 5 bar
No preparation is needed
Evacuate it (no air) and label it for the specific flammable refrigerant
Purge it with compressed air

368

Közepes

What is the correct approach in a risk analysis before work on an HC system?


Having a fire extinguisher is sufficient
First select PPE, then possibly remove ignition sources
The risk analysis is done after the work is finished
First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)

369

Nehéz

What is the charge limit m₃ = 130 m³ × LFL for R290 (LFL = 0.038 kg/m³) according to IEC 60335-2-40?


approx. 4.94 kg
approx. 0.99 kg
approx. 0.15 kg
approx. 13 kg

370

Közepes

Which property of ammonia helps people detect a leak early?


It is yellow in air
It is odourless
A very low odour threshold (a few ppm)
It is denser than air

371

Közepes

What hazard does a large CO₂ leak in an enclosed room pose to people?


Explosion of the mixture with air
Accumulation near the floor and asphyxiating/toxic effects at high concentrations
CO₂ is completely safe
Formation of hydrogen fluoride

372

Nehéz

Why does the efficiency of transcritical CO₂ systems fall in warm climates, and how is this mitigated?


At high ambient temperatures the system operates transcritically with large throttling losses – parallel compression and ejectors are used, among others
Gas cooler pressure drops – extra charge is added
Efficiency does not depend on climate
CO₂ freezes in the gas cooler – heaters are used

373

Közepes

What is floating head pressure and what does it achieve?


It increases subcooling by flooding the condenser
It lets the condensing pressure fall with ambient temperature, reducing compressor work and raising COP (requires an expansion valve that works at a small pressure difference)
It means switching condenser fans off periodically
It keeps a constant high condensing pressure all year

374

Közepes

How do SEER/SCOP differ from EER/COP?


There is no difference – they are synonyms
SEER/SCOP are seasonal indicators accounting for part load and climate (EN 14825); EER/COP refer to a single operating point (EN 14511)
SEER/SCOP apply only to natural-refrigerant equipment
EER/COP are always higher than SEER/SCOP

375

Közepes

Which design approach can significantly reduce the F-gas charge of a large refrigeration installation?


An indirect (secondary-coolant) system or a cascade with a natural refrigerant in the low stage, plus heat exchangers with small internal volume
Adding a second liquid receiver
Larger liquid-line diameters
Omitting pipe insulation

376

Közepes

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Because R290 is more expensive than HFCs
Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak
Because extra R290 improves efficiency
Because scales are not needed – charging is done by sight glass

377

Közepes

Which information must be entered in the equipment records after a leak check?


The date and result of the check and the identity of the undertaking and person who performed it (with certificate number)
Only the operator's signature
Only the date of the check
Only the equipment's energy consumption

378

Közepes

What must be done when an indirect method (e.g. parameter analysis) indicates a possible leak?


Record it and check at the next periodic inspection
Carry out a direct-method examination to locate the leak
Top up the refrigerant and end the check
Nothing – indirect methods are sufficient