Why do liquid and oil separators in CO₂ systems require particular attention?


Because of very high pressures – adequate PS and protection devices are required
Because sight glasses and level indicators must not be used in CO₂ systems
Because CO₂ is flammable and separators must not be used
Because CO₂ needs no lubrication, so oil separators are unnecessary

2

Nehéz

What is the critical pressure of CO₂ (R744)?


Approx. 10 bar
Approx. 31 bar
Approx. 74 bar (abs)
Approx. 120 bar

3

Nehéz

What characterises the transcritical process in CO₂ systems?


Heat rejection takes place above the critical point – the refrigerant does not condense in the conventional way (gas cooler instead of condenser)
Conventional condensation occurs
It occurs only at low temperatures
It is irrelevant to system operation

4

Nehéz

What characterises the subcritical CO₂ process?


The absence of condensation
The conventional condensation process below the critical point
The absence of evaporation
Operation above the critical point

5

Nehéz

When can dry ice (solid CO₂) form?


When the pressure drops suddenly below the triple point (approx. 5.2 bar abs, −56.6 °C), e.g. when venting liquid CO₂ or charging liquid into an evacuated system
At high pressure
During normal operation of the system
At high temperature

6

Nehéz

What risks are associated with dry ice forming in a CO₂ system?


No risk
Blocked pipes and valves and system damage (and a sharp pressure rise when it thaws)
Improved efficiency
Pressure reduction

7

Nehéz

How does CO₂ saturation pressure change as temperature increases?


It remains the same
It increases rapidly
It decreases
It first decreases, then increases

8

Nehéz

What happens to CO₂ above the critical point?


It turns into a liquid
It ceases to conduct heat
It turns into a solid
It transitions to a supercritical state (no distinction between liquid and gas)

9

Nehéz

What is the main characteristic of R744 (CO₂) refrigeration systems?


Low operating pressures
Very high operating pressures
Low energy efficiency under all conditions
No need for control

10

Nehéz

What are the requirements for piping materials in CO₂ systems?


Only plastics
It doesn't matter
Any material may be used
They must withstand high pressures (e.g. stainless steel, high-strength copper-alloy tubes such as K65)

11

Nehéz

How does a booster system work in CO₂ installations?


Low-temperature (LT) compressors discharge into the suction of medium-temperature (MT) compressors – two-stage compression in a single circuit
It reduces the refrigerant quantity
It is used to store refrigerant
It reduces evaporator pressure

12

Nehéz

Why is pressure optimisation in CO₂ systems crucial?


It reduces the amount of refrigerant
It enables the system to achieve maximum energy efficiency in transcritical mode
It doesn’t matter
It reduces the ambient temperature

13

Nehéz

What role does parallel compression play in CO₂ systems?


It compresses flash gas from the intermediate receiver directly to high pressure, improving efficiency
It increases energy consumption
It has no significance
It lowers the ambient temperature

14

Nehéz

How does an ejector work in a CO₂ system?


It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
Stores the refrigerant
It increases the amount of refrigerant
It lowers the evaporator temperature

15

Nehéz

What is the function of liquid ejectors in CO₂ systems?


They reduce atmospheric pressure
They raise the refrigerant temperature
They return liquid from the separator and allow partially flooded evaporator operation (better evaporator feed)
They increase the amount of oil

16

Nehéz

What are the characteristics of partially flooded systems in CO₂ systems?


Lack of regulation
The absence of liquid in the evaporator
Low operating pressure
The presence of liquid in the evaporator, which improves heat transfer and efficiency

17

Nehéz

What is the main risk associated with standstill pressure in CO₂ systems?


Increased efficiency
A decrease in refrigerant quantity
A pressure rise as the refrigerant warms up during standstill (possibly exceeding PS and lifting the relief valves)
A drop in temperature

18

Nehéz

How is standstill pressure limited in CO₂ systems?


By using an auxiliary standstill (stagnation) cooling unit, e.g. cooling the receiver, with back-up power, and by selecting an adequate PS and relief valves
By completely shutting down the system and power supply
By increasing the refrigerant charge
By raising the plant-room temperature

19

Nehéz

What does standstill (stagnation) of a CO₂ system mean, and why is it important?


Improved efficiency
A state with no compressor operation or refrigerant flow – pressure rises with ambient temperature and may exceed PS
Normal system operation
A drop in system temperature

20

Nehéz

Which safety class applies to R744?


A3
B2L
A2.
A1

21

Nehéz

In a simple single-stage R744 system without an intermediate receiver (refrigerant flows from the gas cooler directly to the expansion valve), operating transcritically at 90 bar with a gas-cooler outlet temperature of 35 °C, the refrigerant upstream of the expansion valve is…


…a subcooled liquid
…a two-phase mixture at intermediate pressure
…a supercritical fluid
…saturated vapour at intermediate pressure

22

Nehéz

In R744 transcritical systems, the gas cooler outlet valve controls:


The gas cooler fans
The inlet temperature to the gas cooler
The outlet temperature of the gas cooler
The pressure in the gas cooler

23

Nehéz

What is the main reason for using K65 copper tubing in some R744 systems?


They bend easily
They have good low-temperature performance
They can withstand higher pressures
They come in a wider range of diameters

24

Nehéz

Why should an evacuated R744 system initially be charged with refrigerant in the vapour phase?


To charge R744 more slowly and measure it more accurately
To prevent dry ice forming (until approx. 5.2 bar abs is exceeded)
To avoid damaging the compressor with liquid CO₂
To prevent the drain valve on the receiver from opening

25

Nehéz

If moisture remains in an R744 system because it was not properly evacuated (dehydrated), what is the likely consequence?


Formation of carbonic acid, which damages the system
Excessive discharge pressure
Reduced cooling capacity
Formation of hydrogen fluoride and hydrofluoric acid

26

Nehéz

The pressure of R744 at a saturation temperature of 20 °C is approx.


14 bar g
90 bar g
25 bar g
56 bar g

27

Nehéz

At an ambient temperature of 25 °C, the standstill pressure in the low-pressure stage of an R744 cascade (without standstill cooling) will typically be…


…approx. 27.5 bar g
…the same as the relief valve set pressure
…higher than the maximum allowable pressure (PS) of the low-pressure stage
…the same as the high-pressure switch setting

28

Nehéz

What is the correct definition of critical temperature?


The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which, for certain substances, electrical resistance is zero
The temperature above which there are no distinct liquid and gaseous phases
The temperature at which a substance changes from a gaseous to a solid state

29

Nehéz

In the gas cooler of a transcritical system, the supercritical working fluid…


…rejects heat as its pressure falls
…rejects heat during a phase change
…rejects heat at constant temperature and pressure
…rejects heat as its temperature falls

30

Nehéz

Why does the efficiency of transcritical CO₂ systems fall in warm climates, and how is this mitigated?


At high ambient temperatures the system operates transcritically with large throttling losses – parallel compression and ejectors are used, among others
Efficiency does not depend on climate
Gas cooler pressure drops – extra charge is added
CO₂ freezes in the gas cooler – heaters are used