F-Gas English Low GWP

Všetky otázky
HFC | Flammable | CO₂ | NH₃
Ľahké otázky | Stredne ťažké otázky | Ťažké otázky

1

Ľahká


2

Ľahká

What is the base unit of mass in the International System of Units (SI)?


kg
lb (pound)
t
N

3

Ľahká

The refrigerant absorbs heat when…


…it evaporates
…it freezes
…it condenses
…it is subcooled

4

Ľahká

What does the GWP indicator mean?


The annual rise in mean air temperature caused by the emission of 1 kg of the gas
Ozone depletion potential
Global Warming Potential: the climate warming impact of 1 kg of a gas compared with 1 kg of CO₂ (GWP = 1) over a defined time horizon, usually 100 years
The ability of a substance to restore the ozone layer

5

Ľahká

What is the main function of a safety valve?


Prevents the evaporator from freezing
It monitors the moisture content of the refrigerant
Discharges refrigerant when the set pressure is exceeded
It controls the oil level in the compressor

6

Ľahká

What is the unit of pressure in the International System of Units (SI)?


Pa (pascal)
bar (gauge)
atm (standard atmosphere)
psi (pound per square inch)

7

Ľahká

What is the log(p)-h diagram for CO₂ used for?


For analysing thermodynamic processes in a refrigeration system
To measure temperature
To detect leaks
To regulate pressure

8

Ľahká

What can be read from the log(p)-h graph?


Only the humidity
Pressure, enthalpy, temperature and state of the refrigerant
Only the amount of refrigerant
Only the temperature

9

Ľahká

What are CO₂ saturation tables used for?


To regulate the compressor
To determine the oil quantity
To measure humidity
To determine the relationship between temperature and pressure at saturation

10

Ľahká

What does the CO₂ saturation state mean?


A state of high pressure
Dry ice state
Equilibrium between the liquid and vapour phases
A state in which the refrigerant is only a gas

11

Ľahká

Why is understanding the log(p)-h graph particularly important for CO₂?


It doesn’t matter
As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It only applies to NH₃
It is only used for design purposes

12

Ľahká

Why do CO₂ systems require precise pressure control?


They do not require control
Because there are no valves
Due to low pressures
Due to significant pressure changes with temperature fluctuations

13

Ľahká

What is the basic requirement when charging a system with R717 (NH₃)?


Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging must only take place at temperatures below 0°C
NH₃ can be charged together with air
Charging can be carried out without personal protective equipment

14

Ľahká

What is the correct procedure for recovering R717 from a system?


Recovery is not required
The gas can be released into the atmosphere
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The refrigerant can be drained into the sewer system

15

Ľahká

How should R717 (NH₃) be stored?


In unmarked plastic containers
In any open containers
In sealed, labelled containers, in a cool and well-ventilated place
Near heat sources

16

Ľahká

What is the main hazard associated with an R717 leak during maintenance work?


Increased cooling efficiency
Damage to electrical equipment only
No risk whatsoever
Toxic to humans and may cause chemical burns

17

Ľahká

What personal protective equipment is required when working with NH₃?


Only a safety helmet
Workwear only
No requirements
Safety goggles, gloves and respiratory protective equipment

18

Ľahká

How do system leaks affect compressor energy efficiency?


They improve efficiency because condensing pressure drops
No effect as long as the system still cools
Refrigerant loss reduces capacity and increases energy use (longer run times, higher superheat)
They affect only safety, not energy use

19

Ľahká

How does a dirty condenser affect the operation of the refrigeration system?


It improves efficiency
Causes an increase in pressure and energy consumption by the compressor
It lowers the condensing pressure
It has no effect

20

Ľahká

Why is adequate airflow through an air-cooled condenser important?


It ensures effective heat rejection and low condensing pressure
It affects only noise
It doesn't matter
The lower the airflow, the lower the condensing pressure

21

Ľahká

How does the presence of limescale in a water-cooled condenser affect performance?


Impairs heat exchange and increases energy consumption
It has no effect
It improves heat transfer
It lowers the condensation temperature

22

Ľahká

How do condenser leaks affect energy efficiency?


They improve efficiency
Causes refrigerant loss and a drop in efficiency
Have no effect
They lower the temperature

23

Ľahká

How important is the correct positioning of an air-cooled condenser?


It should be housed in a small room
It should be close to heat sources
It should be installed in a well-ventilated area with unobstructed airflow
It doesn’t matter

24

Ľahká

How does hot air recirculation affect the condenser?


It reduces the pressure
It improves efficiency
Impairs cooling and increases energy consumption
It has no effect

25

Ľahká

How does evaporator icing affect the system’s operation?


It has no effect
It lowers the condensation temperature
It improves cooling performance
Impairs heat exchange and increases energy consumption

26

Ľahká

How does dirt on the evaporator surface affect its performance?


Impairs heat exchange and increases energy consumption
It reduces the pressure
It has no effect
It improves efficiency

27

Ľahká

What maintenance task is crucial for the evaporator?


Regular cleaning and defrosting
Increasing the refrigerant charge
Lack of maintenance
Reduced airflow

28

Ľahká

How does superheat at the evaporator outlet affect efficiency?


It always improves performance
It has no effect
It only causes a temperature drop
Excessive superheat reduces energy efficiency

29

Ľahká

How do leaks in the evaporator affect efficiency?


These cause refrigerant loss and a drop in efficiency
Increase capacity
Have no effect
Improves performance

30

Ľahká

How important is correct expansion valve adjustment?


It increases energy consumption
It doesn’t matter
Ensures optimal evaporator charge and improves efficiency
Causes leaks

31

Ľahká

How does inadequate insulation of suction (or secondary-coolant) pipes affect evaporator performance?


It causes cooling losses and increased energy use
It lowers the condensing temperature
It improves efficiency
It has no effect

32

Ľahká

How does correct TEV adjustment affect system energy efficiency?


It causes leaks
It ensures optimal superheat and improves efficiency
It has no effect
It increases energy use

33

Ľahká

What happens if the superheat set by the TEV is too high?


The refrigerant charge will increase
It has no effect
Cooling efficiency will improve
Efficiency will drop because the evaporator is not being fully utilised

34

Ľahká

How do contaminants in the system affect the operation of the TEV?


They improve its performance
They can cause it to become blocked and reduce efficiency
Have no effect
They lower the temperature

35

Ľahká

What role does the filter-drier play in terms of system efficiency?


Removes moisture and contaminants, improving the system’s efficiency
It lowers the temperature
It doesn’t matter
It increases the amount of refrigerant

36

Ľahká

How does proper insulation of components (e.g. pipes near the TEV) affect the system?


Prevents unwanted heat gains and improves efficiency
It increases energy consumption
It causes leaks
It doesn’t matter

37

Ľahká

How important is it to check the operation of the condensing pressure control valve in the system?


It increases energy consumption
It causes a significant rise in temperature
Ensures operation within the optimum pressure range and reduces energy losses
It has no effect

38

Ľahká

How does the correct selection of a TEV affect energy efficiency?


It increases the amount of refrigerant
It lowers the temperature
It doesn’t matter
Ensures the system is matched to its capacity and operates optimally

39

Ľahká

What is the function of high-pressure control valves in CO₂ systems?


They regulate oil flow
They control the pressure on the high-pressure side and optimise system operation
They lower the evaporator temperature
They are used to store the refrigerant

40

Ľahká

Why do CO₂ systems require more advanced automation than traditional systems?


Due to the need for precise control of pressure and temperature
They do not require automation
Because there are no valves
Due to low pressures

41

Ľahká

What is the requirement regarding the labelling of an installation containing a flammable substance?


The labelling must indicate the type of substance and the flammability hazard
Colour-coding of pipes is sufficient
Labelling is not required for hermetically sealed systems
Labelling is required only in technical rooms

42

Ľahká

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


No impact on safety
Merely installation difficulties
Risk of leakage and the formation of an explosive mixture
Merely a reduction in efficiency

43

Ľahká

How should an employee respond when a gas alarm is triggered?


Carry on working until they see a leak
Reduce the pressure in the system
Leave the room immediately and notify their supervisor
Switch off the system and wait for the alarm to stop

44

Ľahká

Gas detectors should be installed in rooms where:


Ventilation is natural
The room is less than 5 m²
The amount of refrigerant exceeds a specified permissible threshold
Any refrigerant is present, regardless of the quantity

45

Ľahká

How do leaks affect systems using flammable refrigerants?


They cause refrigerant loss, reduced efficiency and a fire hazard
Have no effect
They lower the temperature
They improve efficiency

46

Ľahká

Why is the cleanliness of heat exchangers in HC systems important?


It increases the pressure
It improves heat transfer and reduces energy consumption
Causes leaks
It doesn’t matter

47

Ľahká

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Disabling safety devices
Increasing the refrigerant charge
Regular checks for leaks and operating parameters
Lack of servicing

48

Ľahká

How does the correct selection of components affect a system using a flammable refrigerant?


It lowers the temperature
It increases the amount of refrigerant
It ensures safe and optimal operation and minimises energy losses
It doesn’t matter

49

Ľahká

Why is it important to use the correct service tools in HC systems?


It doesn’t matter
Causes leaks
It increases energy consumption
It ensures operational safety and reduces refrigerant losses

50

Ľahká

How does pipe insulation affect the efficiency of systems containing HC?


Causes leaks
It increases the pressure
It reduces energy losses and improves efficiency
It doesn’t matter

51

Ľahká

What is the base unit of temperature according to the International System of Units (Système International d’Unités)?


K
°R
°F
°C

52

Ľahká

What is the superheat of refrigerant vapour?


The amount of heat required to evaporate a liquid
The difference between the saturation temperature and the actual liquid temperature in the liquid line
The difference between the condensing temperature and the ambient temperature
The difference between the actual vapour temperature and the saturation temperature corresponding to its pressure (expressed in K)

53

Ľahká

What is the compression ratio of a compressor?


The ratio of suction pressure to discharge pressure (po/pc)
The amount of refrigerant compressed per cycle relative to heat capacity
The ratio of discharge pressure to the effective capacity of the compressor (p/Vk)
The ratio of absolute discharge pressure to absolute suction pressure (pc/po)

54

Ľahká

What is the theoretical displacement (swept volume flow) of a compressor?


The volume of refrigerant flowing in one piston cycle under actual operating conditions
The volume of a single cylinder in cm³
The volume of vapour drawn in per unit of time, determined by the compressor's geometry and speed (stated by the manufacturer, e.g. in m³/h)
A value expressed by the coefficient of performance (COP)

55

Ľahká

What is the clearance (dead) volume of a reciprocating compressor?


The volume between the valve plate and the piston crown at top dead centre
The space between the underside of the piston and the crankcase cover
The space between the side of the piston and the cylinder
The volume between the valve plate and the piston at bottom dead centre